Справочник Пользователя для Fluke 1652C07-TPOLEKITVDE-tester 4426040
Модели
4426040
Electrical
Installation
Tester
Specifications
55
RCD/FI-Tripping Current Measurement/Ramp Test (I
Δ
N
)
Dwell Time
Current Range
Step Size
Type G
Type S
Measurement
Accuracy
30 % to 110 % of
RCD rated current
RCD rated current
[1]
10 % of I
Δ
N
[2]
300 ms/step
500 ms/step
±
5 %
Notes
[1] 30 % to 150 % for Type A I
[1] 30 % to 150 % for Type A I
Δ N
>10 mA
30 % to 210 % for Type A I
Δ N
= 10 mA
20 % to 210 % for Type B
Specified trip current ranges (EN 61008-1):
50 % to 100 % for Type AC
35 % to 140 % for Type A (>10 mA)
35 % to 200 % for Type A (
Specified trip current ranges (EN 61008-1):
50 % to 100 % for Type AC
35 % to 140 % for Type A (>10 mA)
35 % to 200 % for Type A (
≤
10 mA)
50 % to 200 % for Type B
[2] 5% for Type B
Earth Resistance Test (R
E
)
Models 1653B and 1654B Only. This product is intended to be used to measure
installations in process plants, industrial installations, and residential applications.
installations in process plants, industrial installations, and residential applications.
Range Resolution Accuracy
200
Ω
0.1
Ω
±
(2 % + 5 digits)
2000
Ω
1
Ω
±
(3.5 % + 10 digits)
Range: RE + R
PROBE
[1]
Test
Current
2200
Ω
3.5 mA
16000
Ω
500
μ
A
52000
Ω
150
μ
A
Note
[1] Without external voltages
[1] Without external voltages
Frequency Output
Voltage
128 Hz
25 V
Live Circuit Detection
Inhibits test if terminal voltage >10 V ac is
detected prior to start of test.
detected prior to start of test.