Wiring of the SECU-DATA xxxx:
1. For the wiring use round wires of type: 0,08
– 2,5mm
2
cross section,
AWG 28
– 12, flame propagation characteristics as per IEC 60332-
1-2, within a round cable to ensure the water protection
2. Strip the wires off app. 5-6 mm
3. Depress each of the levers of the terminal block (Type WAGO se-
ries 256) with a small screw driver
4. Put the stripped wire end into the terminal and release the lever
again
5. Close the SECU-DATA xxxx housing again and mount it to the final
location with the supplied screws in the provided holes of the hous-
ing. Take care for correct positioning of the sealing elements. For
metal base planes ensure that there is some space between the
RF-antenna and the metal material to maintain the best effective
range of the RF connection.
ing. Take care for correct positioning of the sealing elements. For
metal base planes ensure that there is some space between the
RF-antenna and the metal material to maintain the best effective
range of the RF connection.
Remark: After delivery one cable gland is sealed waterproof with a cap.
This is useful if only one cable gland shall be used.