Soft starter 3RW40 2, 3RW40 3, 3RW40 4
English
English
Read and understand these instructions before installing, operating, or maintaining the equipment.
Permitted setpoint values for the motor current, dependent on the CLASS setting at 40 °C surrounding air temperature
1. Start programming mode: (For the 3RW40 2 device, remove the cover as shown in Figure 2.) Press and hold the "RESET MODE" button (2) for 
longer than 2 seconds until the LED "DEVICE" (5) flickers green. While pushing the "RESET MODE" button (2), press the "RESET/TEST" button 
(1) for longer than 1 second until the LED "DEVICE" (5) on the device lights up red.
2. Display mode: LED "STATE/BYPASSED/FAILURE" (6) flashes green: ON mode. LED "STATE/BYPASSED/FAILURE" (6) flickers green: RUN 
mode.
3. Change mode:
 
Press the "RESET MODE" (2) button.
 
4. Exit programming mode and save settings:
 
Press and hold the "RESET/TEST" button (1) for longer than 1 second until the LED "DEVICE" (5) 
lights up green.
 DANGER
CAUTION
Hazardous voltage.
Will cause death or serious injury.
Turn off and lock out all power supplying this device 
before working on this device.
Reliable functioning of the equipment is only ensured with certified 
components.
 DANGER
Hazardous voltage.
Will cause death or serious injury.
The terminals of the motor control device must not be touched when it is connected to a voltage in order to prevent electrical shocks or 
burning. The output terminals of the motor control device are connected to a voltage even when it is in the OFF state.
Stand-alone installation spacings (see soft starter manual for side-by-side installation)
Setpoint values for motor current
I
e
 [A]
I
min
 [A]
I
max
 [A] CLASS 10 
I
max
 [A] CLASS 15 
I
max
 [A] CLASS 20 
3RW40 24-... 12.5
5
12.5
11
10
3RW40 26-... 25.3
10.3
25.3
23
21
3RW40 27-...
32.2
17.2
32.2
30
27
3RW40 28-...
38
23
38
34
31
3RW40 36-...
45
22.5
45
42
38
3RW40 37-...
63
25.5
63
50
46
3RW40 38-...
72
34.5
72
56
50
3RW40 46-...
80
42.5
80
70
64
3RW40 47-...
106
46
106
84
77
Programming the ON/RUN output 13/14 (factory setting: ON) (Fig. 3 in graphics section)
!
!
1
1
3
5
2
4
6
a
≥ 60 mm
[
≥ 2.36 in]
≥ 40 mm
[
≥ 1.56 in]
NOTICE
Please adhere to the specified spacings when installing the device so that sufficient air can 
circulate for ventilation. The unit is ventilated from bottom to top.
CAUTION
Risk of damage to property.
Ensure that no liquids, dust or conductive parts enter the soft starter.
NOTE
Surrounding air temperature - A rating assigned to open type equipment that refers to the 
maximum ambient temperature of air immediately surrounding the equipment inside of the 
ultimate enclosure.
a
a) 3RW40 2: 15 mm [0.59 in]
 
3RW40 3; 3RW40 4: 30 mm [1.18 in]