Техническая Спецификация для Siemens 3RW4024-1BB14 SIRIUS 3RW4024 Soft Starter 3/5.5kW 3RW4024-1BB14

Модели
3RW4024-1BB14
Скачать
Страница из 32
6
3ZX1012-0RW40-2DA1
English
Quick commissioning instructions 
1. Switch off soft starter
(IN 1 -> 0).
2. Reduce startup time (turn 
potentiometer anti-
clockwise).
or
3. Increase limit value if the 
current limit is set (turn 
potentiometer clockwise).
1. Switch soft starter 
off (IN 1 -> 0).
2. Increase startup 
time (turn potentio-
meter clockwise).
3. Reduce current limit 
value (turn 
potentiometer anti-
clockwise).
1. Switch off soft starter
(IN 1 -> 0).
2. Increase start voltage 
(turn potentiometer 
clockwise)
or
3. Increase limit value if the 
current limit is set (turn 
potentiometer clockwise).
1. Switch soft starter 
off (IN 1 -> 0).
2. Reduce start 
voltage (turn 
potentiometer anti-
clockwise).
The motor reaches 
its nominal rotational 
speed 
- with a torque 
increase that is too 
high 
- faster than desired, 
with a startup 
current that is too 
high
The motor reaches 
its nominal 
rotational speed 
- slower than 
desired 
- not at all 
(motor stuck)
The motor 
hums and 
does not 
start 
immediately
Motor: 
The motor 
starts with a 
sudden 
increase in 
torque
Increase stopping time (turn 
potentiometer clockwise)
Reduce stopping time (turn 
potentiometer anticlockwise)
Soft stopping
The motor stops 
abruptly and not 
softly.
The motor keeps 
going for too long.
Quick commissioning of 
the 3RW40 SIRIUS 
soft starter
1. Wiring control 
- Control part and 
- Performance part
2. Configure device
Motor protection
- Set the rated motor current of the device using the I
e
 
controller
- Set the required tripping class with the CLASS switch.
Set the soft start function
- Current limit value (x I
e
)
- Startup time (s)
- Start voltage (%)
- Stopping time (s)
to the desired value (see table for suggested settings).
3. Check and connect the 
voltages in the control and 
main circuits.
Determine and rectify the 
cause of the fault using the 
LED display and the status 
table (see Page 7).
"DEVICE" LED
cont. green light,
are the other LEDs 
off?
No
4. Switch soft starter 
on (IN 0 -> 1)
LEDs:
"DEVICE" cont. green 
light, "STATE/BYPASSED" 
flashing green?
Does 
the motor 
start softly?
Does 
the motor reach 
its nominal rotational speed 
quickly and within the 
desired time?
LEDs:
"DEVICE" cont. green light, 
"STATE/BYPASSED" green 
cont. light?
Switch soft starter 
off (IN 1 -> 0)
Which type of 
stopping has been 
selected?
Motor 
 reaches stationary 
state as desired?
End of 
commissioning
Motor: 
No
No
No
No
No
Thermistor connection (3RW40.-.TB0. only)
– Thermoclick connection according to Fig. 6.3 (remove jumper)
– PTC connection type A according to Fig. 6.4 (remove jumper)
CAUTION
Risk of damage to property.
Connection to an unassigned terminal is not permitted.
Suggested setting
Startup parameters
Stopping 
parameters
Start
voltage %
Startup 
time s
Current limit
value
Stopping time s
Application
Conveyor belt
70
10 
5 x I
e
5
Roller conveyor
60
10
5 x I
e
5
Compressor
50
10
4 x I
e
0
Small fan
40
10
4 x I
e
0
Pumps
40
10
4 x I
e
10
Hydraulic pump
40
10
4 x I
e
0
Stirrers
40
20
4 x I
e
0
Milling machines
40
20
4 x I
e
0
40
100%
0
5
10
20s
e
x I
5
1.3
5
10
0
20s
Soft stopping
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Coasting down