12. Connect the BOP to the new inverter.
13. Ensure power is applied to the inverter.
14. Set parameter P0003 to 3.
15. Set parameter P0010 to 30 to enter Cloning Mode.
16. Set parameter P0803 to 1 to start the download from the BOP to the
13. Ensure power is applied to the inverter.
14. Set parameter P0003 to 3.
15. Set parameter P0010 to 30 to enter Cloning Mode.
16. Set parameter P0803 to 1 to start the download from the BOP to the
inverter.
17. During the download “BUSY” will be displayed.
18. During download the BOP and the inverter will not react to any commands
18. During download the BOP and the inverter will not react to any commands
during download.
19. If the download has been completed successfully, the BOP display will
return to normal and the inverter will return to a ready state.
20. If the download has failed:
a. Attempt another download.
or
b. Perform a factory reset.
21. The BOP can now be removed from the inverter.
The following important restrictions should be considered when using the Cloning
procedure:
Only the current dataset is uploaded to the BOP.
Once the cloning procedure has started, it cannot be interrupted.
It is possible to copy data from inverters of different power and voltage ratings.
During download, if the data is not compatible with the inverter, the default
values for the parameter will be written to the inverter.
values for the parameter will be written to the inverter.
During the cloning process any data already held by the BOP is overwritten.
If the download or upload of data fails, the inverter will not function correctly.
Note
After cloning parameters between differing variants of the SINAMICS G110
inverters (i.e. Analog to USS or USS to Analog) the following parameter must be
checked:
P0719 – Selection of command and frequency setpoint
P1000 – Selection of frequency setpoint.