Using the SINAMICS G110
SINAMICS G110 Operating Instructions
6SL3298-0AA11-0BP0
53
Reversing the motor
Analog Variant
Default value:
2 – Terminal 4 (DIN 1, high)
Other settings:
see P0701 to P0704 in the Parameter List
USS Variant
Default value:
5 – Terminals 8 & 9 (RS485); control word 1 (r0054), bit 11
4.3 OFF and braking Functions
4.3.1 OFF1
This command (produced by canceling the ON command) causes the inverter to
come to a standstill at the selected ramp-down rate.
come to a standstill at the selected ramp-down rate.
Parameter to change ramp-down time see P1121
NOTES
ON and the following OFF1 command must have the same source.
If the ON/OFF1 command is set to more than one digital input, only the last set
digital input is valid.
digital input is valid.
OFF1 can be combined with DC braking.
4.3.2 OFF2
This command causes the motor to coast to a standstill (pulses disabled).
NOTE
The OFF2 command can be actuated from any command source simultaneously.
NOTE
The OFF2 command can be actuated from any command source simultaneously.
4.3.3 OFF3
An OFF3 command causes the motor to decelerate rapidly.
Ramp down time:
see P1135
NOTE
OFF3 can be combined with DC braking.
OFF3 can be combined with DC braking.
4.3.4 DC braking
DC braking is possible together with OFF1 and OFF3. A DC current is applied to
stop the motor quickly and hold the shaft stationary until the end of the braking
period. The stator resistance value must be entered into P0350 for the DC braking
to work correctly.
stop the motor quickly and hold the shaft stationary until the end of the braking
period. The stator resistance value must be entered into P0350 for the DC braking
to work correctly.
Enable DC braking:
see P0701 to P0704
Set DC braking period:
see P1233
Set DC braking current:
see P1232
NOTE
If no digital input is set to DC braking and P1233
If no digital input is set to DC braking and P1233
≠ 0, DC braking will be active after
every OFF1 command with the time set in P1233.