Using the SINAMICS G110 
SINAMICS G110    Operating Instructions 
 
6SL3298-0AA11-0BP0 
53
 
Reversing the motor 
Analog Variant 
 
Default value: 
2 – Terminal 4 (DIN 1, high) 
 
Other settings: 
see P0701 to P0704 in the Parameter List 
 
USS Variant 
 
Default value: 
5 – Terminals 8 & 9 (RS485); control word 1 (r0054), bit 11 
 
4.3  OFF and braking Functions  
4.3.1 OFF1 
This command (produced by canceling the ON command) causes the inverter to 
come to a standstill at the selected ramp-down rate. 
Parameter to change ramp-down time see P1121 
NOTES 
 
ON and the following OFF1 command must have the same source.  
 
If the ON/OFF1 command is set to more than one digital input, only the last set 
digital input is valid. 
 
OFF1 can be combined with DC braking. 
4.3.2 OFF2 
This command causes the motor to coast to a standstill (pulses disabled). 
NOTE 
The OFF2 command can be actuated from any command source simultaneously. 
4.3.3 OFF3 
An OFF3 command causes the motor to decelerate rapidly.  
 
Ramp down time: 
see P1135 
NOTE 
OFF3 can be combined with DC braking. 
4.3.4 DC braking 
DC braking is possible together with OFF1 and OFF3. A DC current is applied to 
stop the motor quickly and hold the shaft stationary until the end of the braking 
period. The stator resistance value must be entered into P0350 for the DC braking 
to work correctly. 
 
Enable DC braking:   
 
see P0701 to P0704 
 
Set DC braking period:  
 
see P1233 
 
Set DC braking current:  
 
see P1232 
NOTE 
If no digital input is set to DC braking and P1233 
≠ 0, DC braking will be active after 
every OFF1 command with the time set in P1233.