Техническая Спецификация для Novatek CONTROL UNIT REFRIGERATING MSK-102-1 MSK-102-1

Модели
MSK-102-1
Скачать
Страница из 7
- 2 - 
MCK-102-14   
                                                                                                                                                                
NOVATEK-ELECTRO
 
1 APPLICATION 
 
Temperature controller MCK-102-14 (hereinafter MCK-102-14) is designed for the control and operation 
by deep-freezing machines, commercial refrigeration displays, monoblock units and other similar refrigeration 
equipment.  
Basic functions that performs MCK-102-14are the following: 
-  temperature control over refrigerated zone;  
-  automatic defrost by turning OFF the compressor for certain time adjusted by user; 
-  compressor protection from voltage drops and unallowable voltage fluctuations – this is achieved by 
permanent control of the acting voltage measurement and control; 
-  automatic restart of the compressor when the voltage parameters returned back to normal values after 
the voltage interruption. Auto-restarting time delay could be adjusted by user as necessary. 
digital filtration of signal is added from the sensor of temperature  (menu item “”). 
 
ATTENTION! If MCK-102-14 is powered by 24V DC, then the power supply unit must necessarily be 
galvanically isolated from mains 220V/50Hz voltage (it should withstand testing RMS voltage of 1500V 
during 1 minute). 
Please also pay attention that in case of powering the MCK-102-14 with 24V DC the voltage 
monitoring function should necessarily be disabled (parameter 
 should be set to “0”).  
 
N o t i c e - On special request it is possible to supply the programming device for the  
MCK-102-11 to change default factory settings. 
 
 
2 MAIN FEATURES 
 
•  Analog input for connection of the NTC temperature sensor with reinforced insulation for the precise 
temperature control in refrigerated zone; 
•  Temperature measurement discrimination –  0,1 
o
C; 
•  Normally open relay output for the operation by refrigeration compressor – 250V 16A at cosϕ=1; 
•  Accuracy for the measurement of voltage tripping thresholds – not more than 3V; 
•  Rated power supply voltage: Single phase ~240V, 50 Hz or alternatively –24V DC (±10%); 
•  Maximal allowed operational voltage is up to 400V 50 Hz; 
•  Rated power is not more than 5W; 
•  Frontal side protection degree: IP65; 
•  Wiring terminals protection degree: IP20; 
•  Operational temperature range: from  –35 to +55 
o
C; 
•  Storage temperature: from  –45 to +65 
o
C; 
•  Weight: not more than 150 grams; 
•  Wall mounting position – arbitrary as per requirement; 
•  Control knobs, dimensions and wiring diagram are shown on Figure 1. 
•  Program version – 14. 
 
3 INSTALLATION AND START UP PROCEDURES 
 
3.1 MCK-102-14 should be installed into the case of refrigeration installation or any other suitable place 
that excludes the ingress of moisture inside the case of MCK-102-14.  
During installation special attention should be paid so that all wiring connections must be fixed well such a 
way to avoid twisting and abrasion of the wires. 
 
4 PREPARING FOR OPERATION 
4.1 Connect compressor and temperature sensors to corresponding terminals of MCK-102-14 as shown 
one Figure 1.  
If the rated power of the compressor is more than 1000W or three phase compressor is being used in 
refrigeration installation – then the MCK-102-14 should operate with compressor via contactor. So that MCK-
102-14 will operate with the magnetic coil of the contactor of corresponding rated parameters and contactor 
in its turn will commutate (turn ON/OFF) the compressor. 
4.2 Connect power supply wires to the MCK-102-14.