Техническая Спецификация для Novatek CONTROL UNIT REFRIGERATING MSK-102-1 MSK-102-1

Модели
MSK-102-1
Скачать
Страница из 7
- 3 - 
NOVATEK-ELECTRO
       
                                                                                                                                                             
MCK-102-14 
                          
 
 
4.3 Turn ON  the power and adjust all necessary parameters and operation modes in accordance with 
Table 2. 
 
ATTENTION!   All wiring connections must be performed only on fully deenergized device. 
 
 
 
 
LED COMP is ON when the compressor is working; 
LED DEF is ON at the process of defrost; 
LED SET is ON at the moment of adjusting the required parameters 
 
Figure 1 - Front panel, wiring diagram, operation knobs and outer dimensions of 
МСК-102-14. 
 
N o t e:    button hereinafter in text – “UP”,    button – “DOWN” 
 
5 OPERATION GUIDELINES 
 
5.1 Initially MCK-102-14 digital display shows current temperature in refrigerated chamber. 
5.2 Operation by the MCK-102-14 should be performed as follows: 
-  On pressing UP  and  DOWN  buttons simultaneously on the digital display within 5 seconds will be 
indicated Set Point temperature (SP), and then within 5 seconds will be shown voltage value on the input of 
the MCK-102-15; 
-  DEF  button should be pressed to start the defrost ahead-of-schedule or premature stop the defrost 
and switch to thermostat mode; 
-  SET button is used to enter to setting menu to view and adjust necessary parameters.  
-  To view and change any parameter SET  button should be pressed and LED  indicator “SET” will turn 
ON. To scroll the parameters use UP and DOWN buttons. To change the parameter value press SET button 
again and set the required value using UP  and  DOWN  buttons. To save the parameter and return back to 
menu press DEF button. To exit menu without saving press SET.  
If none of the buttons are pressed within 15 seconds MCK-102-14 automatically return to its initial state. 
5.3 To restore default factory settings quickly it is necessary to take the following actions: 
  a) Press UP and DOWN buttons simultaneously and while keeping the buttons pressed turn ON power 
supply to the MCK-102-14;