LOGO! functions 
 
4.4 Special functions list - SF 
 
LOGO! 
222
 
Manual, 06/2014, A5E33039675 
Timing diagram 
The nature, manner and speed with which the AQ changes depend on the parameters KC 
and TI. Thus, the course of AQ in the diagram is merely an example. A control action is 
continuous; therefore the diagram portrays just an extract. 
 
1.  A disturbance causes the PV to drop, as Dir is positioned upwards, AQ increases until PV 
corresponds again to SP. 
2.  A disturbance causes the PV to drop, as Dir is positioned downwards, AQ decreases until 
PV corresponds again to SP. 
It is not possible to change the direction (Dir) at runtime of the function. The change is 
shown here for illustrative purposes only. 
3.  As AQ is set to 0 by means of the input R, PV changes. This is based on the fact that PV 
increases, which on account of Dir = upwards causes AQ to drop. 
Functional description 
If the input A/M is set to 0, then the special function issues output AQ with the value that you 
set with parameter Mq. 
If the input A/M is set to 1, then automatic mode commences. As an integral sum the value 
Mq is adopted, the controller function begins the calculations. 
 
 
Note 
For further information on the controller basics, please refer to the Online Help for 
LOGO!Soft Comfort. 
 
The updated value PV is used to calculate in the formulas: 
Updated value PV
 = (PV • gain) + offset