LOGO! functions 
 
4.4 Special functions list - SF 
LOGO! 
Manual, 06/2014, A5E33039675 
223
 
●  If the updated value PV = SP, then the special function does not change the value of AQ. 
●  Dir = upwards (+) (timing diagram numbers 1. and 3.) 
–  If the updated value PV > SP, then the special function reduces the value of AQ. 
–  If the updated value PV < SP, then the special function increases the value of AQ. 
●  Dir = downwards (-) (timing diagram number 2.) 
–  If the updated value PV > SP, then the special function increases the value of AQ. 
–  If the updated value PV < SP, then the special function reduces the value of AQ. 
With a disturbance, AQ continues to increase / decrease until the updated value PV again 
corresponds to SP. The speed with which AQ changes depends on the parameters KC and 
TI. 
If the input PV exceeds the parameter Max, then the updated value PV is set to the value of 
Max. If the PV falls short of the parameter Min, then the updated value PV is set to the value 
of Min. 
If the input R is set to 1, then the AQ output is reset. As long as R is set, the input A/M is 
disabled. 
Sampling time 
The sampling time is fixed at 500 ms. 
Parameter sets 
For more information and application examples with application-related parameter sets for 
KC, TI and Dir, refer to the Online Help for LOGO!Soft Comfort. 
Setting the Par parameter 
View in programming mode (example): 
 
View in parameter assignment mode: