Техническая Спецификация для Phoenix Contact 2900553 ELR H3-ES-SC-230AC/500AC-2 2900553

Модели
2900553
Скачать
Страница из 48
14
3. Connection notes 
3.1. Mains connection and line protection 
CAUTION: Never work when voltage is present!
Life-threatening danger!
• When connecting the 3-phase network, it is essential to observe the terminal identification! 
• Protection:
• The control supply voltage and control voltage inputs must be operated with power supply modules in 
acc. with DIN 19240 (max. 5% residual ripple)!
In devices with 230 V AC activation, always use the same phase for  the control supply 
voltage and the control inputs!
• In order to avoid the inductive or capacitive decoupling of disturbing pulses with long control wires, we 
recommend the use of shielded conductors.
If you want to clamp two conductors under one terminal point, you must use a 
conductor with the same conductor cross-section.
3.2. Block diagram 
25 A (Diazed) - 
Current mains protection in the case of max. cable cross-section 2.5 mm
2
16 A FF (6.3 x 32 mm) - 
Device protection 
16 A (Aut. device B, circuit-breaker) - Short-circuit (1.5 kA network)
20 A (Motor protecting switch) -  Short-circuit (1.5 kA network)
20 A TRS20R20A (fuse) - 
Short-circuit   (5 kA network)
25 A gl-gG (fuse) - 
Short-circuit (10  kA network)
Reset
Reset
Autoreset
Reset 2
MAN
AUT
RES
Logic
µP
24
VDC
s
U
97
96
95
97
96/98
95
& Error
24VDC
ON
E
230
VAC
s
U
230VAC
ON
N
E
N
1/L1
3/L2
5/L3
2/T1
4/T2
6/T3
Fig. 2
ELR H3-ES-230AC/...
ELR H3-ES-24DC/...