4.2.1. Error acknowledgment 
Two different options are available for error acknowledgement:
Manual (Reset button): 
 
An acknowledgement is triggered by actuating the Reset button on the device front side. 
Manual (remote acknowledgement): 
 
A remote acknowledgment operating point can be realized by connecting a button (N/O contact) between 
the MAN and RES terminals. 
An acknowledgement is triggered if a positive edge is identified at the MAN input. If a negative edge is not 
identified after approx 2 s, the hybrid motor starter adopts the error status again since the possibility of a 
manipulation or a defect in the acknowledgement circuit cannot be ruled out.
The RES terminal provides the voltage for a reset. 
 
In variants with the rated control supply voltage of 24 V DC, this is 24 V DC and in the case of 
230 V AC, it is a special system voltage.
4.2.2. Feedback 
If the hybrid motor starter detects an error, the feedback relay is activated, i.e. the N/O contact is closed 
or the N/C contact is opened.
The feedback serves in signaling and is not a part of the safety chain. It is thus not included in the safety 
monitoring.
5. Application examples
5.1. EMERGENCY STOP
Integrating a hybrid motor starter into an EMERGENCY STOP chain is pictured in Fig. 3 (page 47). 
Here, the control voltage supply is switched off via the safety relays, as soon as the EMERGENCY STOP 
button is actuated.
Switching off the control voltage supply with a controlled motor always results in wear in 
the hybrid motor starter. 
This switch should only be used if no more than 10,000 shutdowns can be expected over the entire 
lifespan system.
If the switch-off is performed, for instance, from a "safe controller" with semiconductor outputs, the 
residual voltage must be < 5 V DC. Interruptions ≤ 1 ms are filtered. 
5.2. Safety door (EMERGENCY STOP)
In applications where the safety switch-off is a normal operating mode such as in the case of safety door 
or two-hand applications, a circuit as per Fig. 4 (page 48) should be used.
In this application, the control current circuit is switched and not the control supply voltage.
If the switch-off is performed, for instance, from a "safe controller" with semiconductor outputs, the 
residual voltage must be < 5 V DC. Interruptions ≤ 3 ms are filtered. 
5.3. Motor with brake
If a motor with a brake (connection in the motor terminal block) is connected, the 400 V AC brake must be 
connected to the 2/T1 and 6/T3 connections. A 230 V AC brake should be connected to the 4/T2 
connection and the star point of the motor. 
Please note: The motor current monitoring must be increased by the value of the brake (nominal 
current brake). 
5.4. Auxiliary relay connection
Auxiliary relay (e.g. PLC RSC 230UC/21, Order No.: 2966207) for activating the external brakes or 
feedback to the PLC must be connected to the connection "4T2" and "N" of the system.