Техническая Спецификация для Phoenix Contact 2900553 ELR H3-ES-SC-230AC/500AC-2 2900553

Модели
2900553
Скачать
Страница из 48
17
6. Technical data 
Type
Order No.
ELR H3-ES-SC-  24DC/500AC-0,6
2900550
ELR H3-ES-SC-  24DC/500AC-2
2900552
ELR H3-ES-SC-  24DC/500AC-9
2900554
ELR H3-ES-SC-230AC/500AC-0,6
2900686
ELR H3-ES-SC-230AC/500AC-2
2900553
ELR H3-ES-SC-230AC/500AC-9
2900555
Input data
ELR...-24DC/...
ELR...-230AC/...
Rated control supply voltage U
as per IEC 60947-1 / UL 508
24 V DC
230 V AC (50/60 Hz)
Control supply voltage range
19.2 ... 30 V DC
(32 V DC, max. 1 min.)
85 ... 253 V AC
Control supply voltage
Switching level "Safe off"
< 5 V DC
< 5 V AC
Rated control supply current as per IEC 60947-1
≤ 40 mA
 4 mA
Control input ON:
Switching level "Low"
-3 ... 9.6 V DC
< 44 V AC
Switching level "Safe off"
< 5 V DC
< 5 V AC
Switching level "High"
19.2 ... 30 V DC
85 ... 253 V AC
Input current
 5 mA
 7 mA
Output data
load side
ELR...-0.6
ELR...-2
ELR...-9
Circuit principle
Safety end level with bypass, three-phase 
electrically isolated switch-off
Rated operating voltage U
e
as per IEC 60947-1
500 V AC (50/60 Hz)
Operating voltage range
as per IEC 60947-1
as per UL 508
42...550 V AC
42...500 V AC
Load current at 20°C (see 8.2. Derating curve)
0.075...0.6 A 
0.18...2.4 A 
1.2... 9.0 A
Load current at 20°C without safety function and 
asymmetry recognition (see 8.2. Derating curve)
0... 0.6 A
0...2.4 A
0...9.0 A
Rated operating current I
e
as per IEC 60947-1
AC-51 
as per IEC 60947-4-3
AC-53a
as per IEC 60947-4-2
as per UL 508
0.6 A
0.6 A
0.6 A
2.4 A
2.4 A
2.4 A
9 A
6.5 A
6.5 A
Nominal switching performance
as per UL 508
Full Load (power factor = 0.4)
Full Load (power factor = 0.8)
0.3 kW (0.4 HP)
0.5 kW (0.6 HP)
0.9 kW (1.2 HP)
1.7 kW (2.2 HP)
2.3 kW (3.0 HP)
4.6 kW (6.1 HP)
Leakage current (input, output)
0 mA
0 mA
0 mA
Residual voltage at I
e
< 200 mV
< 300 mV
< 500 mV
Surge current 
100 A (t = 10 ms)
Input protective circuit
Varistors
Short circuit current rating SCCR
acc. to UL 508
- suitable for use on a circuit capable of delive-
ring not more than 5 kA
rms
 symmetrical amperes, 
500 V maximum
- suitable for use on a circuit capable of delive-
ring not more than 100 kA
rms
 symmetrical am-
peres, 500 V maximum when protected by a 
30 A class J or CC fuse