Справочник Пользователя для Patterson-Kelley MOD-04

Скачать
Страница из 54
 Modu-Fire
® 
Gas-Fired Boiler 
Installation 
 
 
 15 
the main burner shuts off (the green "Heat" indicator 
will go out).  The high-limit switch must be manu-
ally reset after testing.  This same check should also 
be made for the "Operating Temperature" control.  
After completion of these tests, readjust thermostats 
to desired operating temperature and set high-limit 
temperature, typically 20º F above operating tem-
perature. 
 
3.11.4  Test of Low Gas Pressure Switch 
 
 
 
Gas Pressure Switch 
 
The boiler is furnished with a low gas pressure 
switch.  The operation of this switch must be 
checked by slowly closing the main gas cock while 
the burner is operating.  The switch should shut 
down the main burner.  When the gas pressure 
switch opens, the "Gas Press." indicator will light.  
Upon reopening the main gas cock, the "Gas Press." 
indicator should remain on until the low gas pres-
sure switch is manually reset.   
 
3.11.5  Test of High Gas Pressure Switch 
The correct setting of the high gas pressure switch is 
essential for proper operation of the boiler.  This 
switch is set by the factory at 4.0” w.c. and must not 
be changed.   
This switch must be checked by factory-trained per-
sonnel. 
 
3.12
  
I
NITIAL 
A
DJUSTMENTS 
 
 
3.12.1A – Configuring the Local Controller  
(Applies to models furnished with programmable 
temperature control.) 
 
Operating Modes: 
  Internal Setpoint 
  Night Setback (Alternate Setpoint) 
  Outdoor Air Reset 
  Analog Input Setpoint  (See Section 3.12.1B.) 
  Analog Input Direct Drive  (Multiple boiler 
Controls) 
 
Definitions: 
SP1-  Setpoint 1: ...................This is the primary 
setpoint of the boiler. 
SP2- Setpoint 2 : ...................An alternate setpoint.  
Available through the 
alternate setpoint con-
tact closure. 
dSP- Differential Setpoint : ..An alternate setpoint 
differential from SP1.  
Available through the 
alternate setpoint con-
tact closure. 
tA-  Air temperature: ............Measurement of out-
side air temperature. 
SP.E- External Setpoint: .......Measurement of the 
external setpoint. 
HyS1:....................................Low temperature dif-
ferential. 
HyS3:....................................High temperature dif-
ferential. 
 
 
Internal Setpoint 
The boiler water outlet temperature is controlled to 
SP1 (setpoint 1) and the boiler modulates to main-
tain SP1 subject to the upper and lower temperature 
differentials and the upper and lower setpoint limit.   
 
 
Manual Reset