 Modu-Fire
® 
Gas-Fired Boiler 
Installation 
 
 
 17 
Analog Input Direct Drive 
The firing rate of the boiler is controlled by an ex-
ternal analog signal, usually from a multiple boiler 
control.  The boiler turns on and off as directed by 
the external control. 
An operating limit control ensures that the boiler 
temperature does not exceed the set value. 
Refer also to Section 3.12.1B. 
 
Use of the Controller 
 
 
 
 
 
The diagram shows the RWF40 after switching on 
power.  This condition is called the basic display. 
The actual value and the currently active setpoint 
are shown here.  Manual operation, self-setting, and 
the user, parameter, and configuration levels can be 
activated from here. 
 
Operation of the Control 
The temperature control has three levels of cascad-
ing menus.  They are: 
  USER level, 
  PARAMETER level, and the  
  CONFIGURATION level.   
The following table indicates the menu options 
available from each level.  The options available 
depend on the operating mode of the boiler. 
 
 
 
User Level: 
  To access the User level from the basic display 
press PGM
  Change the setpoint SP1 with     or  .  
  Change to setpoint SP2 or dSP with PGM.
 
  Change the setpoint SP2 or dSP with    or  . 
 
  Return to the basic display with EXIT. 
 
Manual Operation of the Boiler 
The boiler firing rate can be controlled manually.   
Manual Opera-
tion
EXIT But-
ton
Operating Limit Closed 
Firing Rate Decreasing 
Firing Rate Increasing 
Alarm Relay 
Energized 
Increase 
Value 
Actual Value 
Display (red) 
Setpoint  
Display  
(green) 
Decrease 
Value 
PROGRAM 
Button