Specifications  71 
Fire alarm panel connections 
The electrical layout of the fire alarm system is as described in the schematic drawing supplied with the HP 
POD 40c G2. 
 
Water specifications 
The following table describes the chilled water system specifications for the HP POD 40c G2. 
  
Feature 
Specification 
Facility input temperature to the HP POD 
40c G2 
12ºC to 24ºC (55ºF to 75ºF) 
Working pressure 
1,034 kPa (150 psi) 
HP POD 40c G2 pressure drop 
172.4 kPa (25 psi) 
HP POD 40c G2 water flow rate 
908.5 lpm (240 gpm) 
Chilled water supply and return 
connections 
 
North America—Two 10.16 cm (4 in) ASME B16.5 class #150 
flanges 
 
International—Two DIN PN16 DN100 flanges 
 
 
 
 
Rack specifications 
Standard HP POD 40c G2 racks (AT978A) 
  
Feature 
Specification 
U height 
50U 
Width 
54.6 cm (21.5 in) 
Depth 
99 cm (39 in)* 
Maximum load weight 
1,360.7 kg (3,000 lb) 
 
*This specification indicates the maximum clearance for the cold aisle. Equipment cannot exceed this measurement. 
 
Thermal and air flow performance 
  
Maximum thermal and air flow 
performance parameters 
HP POD 40c G2 specification 
Air temperature—Inlet to rack-mounted 
components) 
Dependent on IT configuration and chilled water inlet temperature 
Chilled water temperature 
12°C to 24°C (55°F to 75°F) 
Total rack-mounted component air flow 
Variable as required to maintain the hot aisle setpoint temperature 
and dependent on IT configuration 
Heat rejection capacity 
600 kW 
 
 
Environmental specifications 
 
Feature 
Specification 
Operating temperature 
-28ºC to 54ºC (-18ºF to 130ºF)