 CGi-4E Gas-Fired Water Boiler — Boiler Manual
Field wiring
6
Thermostat
1.  Connect thermostat as shown on wiring diagram
on boiler.
2. 
Install  on  inside  wall  away  from  influences  of 
drafts, hot or cold water pipes, lighting fixtures, 
television, sunrays, or fireplaces.
3.  If thermostat has a heat anticipator, set heat antici-
pator in thermostat to match power requirements 
of equipment connected to it. If connected directly 
to  boiler,  set  for  0.1  amps  plus  gas  valve  current. 
See  information  on  wiring  diagram  as  shown  in
Figure 31
, page 40. For other devices, refer to manu-
facturer’s specifications. Wiring diagram on boiler 
gives setting for control module and gas valve. Also 
see instructions with thermostat.
Junction Box (furnished)
1.  Connect  120  VAC  power  wiring  as  shown  in
Figure 27
.
2.  Fused disconnect or service switch (15 amp. recom-
mended) may be mounted on this box. For those 
installations with local codes which prohibit installa-
tion of fused disconnect or service switch on boiler, 
install a 2 x 4 cover plate on the boiler junction box 
and mount the service switch remotely as required 
by the code. 
 
For your safety, 
turn  off  electrical  power  supply  at 
service entrance panel before making any electrical 
connections
  to  avoid  possible  electric  shock  hazard. 
Failure  to  do  so  can  cause  severe  personal  injury  or 
death.
 
Wiring must be N.E.C. Class 1.
 
If original rollout thermal fuse element wire as supplied 
with boiler must be replaced, use only type 
200°C
 wire 
or equivalent. If other original wiring as supplied with 
boiler must be replaced, type 
105°C
 wire or equivalent 
must be used.
Boiler  must  be
electrically  grounded
  as  required  by 
National  Electrical  Code  ANSI/NFPA  70–latest  edi-
tion.
Electrical installation must 
comply with:
1.  National  Electrical  Code  and  any  other  national,
state, provincial or local codes or regulations.
2.  In  Canada,  CSA  C22.1  Canadian  Electrical  Code
Part 1, and any local codes.
Wiring connections
Boiler is shipped with controls completely wired.
Figure 27 
 
Field wiring connections — 
service switch and thermostat 
(or end switch) 
provided by installer
 The CGi-4E control module is polarity-sensitive. The hot and neutral wires must be connected
to the correct leads. A flashing POWER light usually indicates reversed polarity of 120 VAC lead
wires.