INSTALLATION 
 
over the marks. Use the mounting  panel  
 
as a template to drill 3/16" holes through  
 
each of the holes marked "A". Install the   
 
replacement control in the freshly drilled holes  
 
in the blower access panel. Use aluminum tape  
 
to seal the unused holes.
B. 
When replacing original 63K8901 board in 
downflow applications
 – Look at the existing 
control board holes as if the unit were installed 
in the upflow position. Make a mark 5/8" 
ABOVE each of the existing mounting holes. 
Position the provided mounting panel so that 
the holes marked "C" in figure 1, page 3 are 
over the marks. Use the mounting panel as a 
template to drill 3/16" holes through each of 
the holes marked "A". Install the replacement 
control in the freshly drilled holes in the blower 
access panel. Use aluminum tape to seal the 
unused holes.
C.  
All other units – Position the provided 
mounting panel so that the arrow on the 
front of the panel is pointing up. Position the 
replacement 50A66-843 ignition control board 
over the holes marked "A" in figure 1, page 3.
 
Insert the replacement control stand-off 
fasteners into the holes in the mounting panel.
 
80UHG, 90UGF, G23, G26, GHR26, G32, 
GHR32, G40, G41, G50, G51, G60 and G61 
units –
 Insert the four provided stand-off 
fasteners into the back of the mounting panel in 
the holes marked "B" in figure 1. 
80MGF, G24M 
and G27M units –  Insert the four provided 
stand-off fasteners into the back of the mounting 
panel into the holes marked "C" in figure 1. 
 
Insert the replacement control board assembly 
into the existing holes in the control box or 
blower panel.
5.  Insert provided circuit breaker in series between 
the blue wire on Pin 3 of the wiring harness (9-pin 
to 12-pin) and the blue transformer wire. Optional 
4" blue wire provided for transformers that have a 
quick-connect terminal.
6.   Connect the provided 9-pin to 12-pin wiring 
harness to the unit 9-pin connector.
7.  Connect the provided 4-pin to 6-pin wiring harness 
to the unit 6-pin connector.
8.  Connect the yellow wire from position 6 on the 12-
pin connector to the yellow transformer wire. 
9.  Connect GND wire to equipment ground.
10.  Connect the remaining 120 VAC hot and neutral 
wires and the flame sense wire to the replacement 
control per table 2, page 5 .
11.  Affix wiring diagram 5001-6972 adjacent to the 
existing unit wiring diagram
12.  Replace the access panel.
13.  Restore the electrical power and gas supply. Refer 
to the furnace installation instructions for start-up 
and check-out procedures.
1.  Disconnect all electrical power and shut off the gas 
supply to the furnace.
2.  Remove the access panel.
3.  Disconnect wiring and remove existing ignition 
control board from the control box.
4.   A. 
When replacing original 63K8901 board  
in upflow or horizontal applications or
downflow applications – Look at the existing  
 
control board holes as if the unit were installed  
 
in the upflow position. Make a mark 1" to the 
 
 
right of each of the existing mounting holes. 
 
 
Position the provided mounting panel so that 
 
 
the holes marked "C" in figure 1, page 3 are  
Optional 4" blue 
wire to connect to 
Transformer (TH)
Circuit breaker
in series between 
Pin 3 and Trans-
former (TH)
Wiring harness
(4-pin to 6-pin)
Mounting panel
Wiring harness
(9-pin to 12-pin)
Transformer
GND
TABLE 1
Type
Existing
Control Board
Replacement 
Control Board
L1
120 VAC
COOL-H
COOL
HEAT-H
HEAT
PARK (2)
PARK (2)
EAC-H
EAC
LINE-H
LINE
XFMR-H
XFMR
HUM-H
HUM
NONE
FAN
Neutral 
120 VAC
LINE-N
Neutral 
120 VAC
(5)
HUM-N
EAC-N
XFMR-N
CIR-N
Flame Sense
E33
FS
PROCEDURE 2 
REPLACING 24L8501, 50A62-120, 50A62-121, 
50A62-820, 56L8301, 63K8901 or 97L4801
Photo 2