Справочник Пользователя для White Mountain DIRECT IGNITION DVD32FP5(0,1,2,3)N-2

Скачать
Страница из 60
23552-5-0608
Page 45
1.  Remove glass door and place away from the fireplace.
2.  Turn on gas shut off valve. Follow ignition procedure.
3.  If burner does not light after spark sequence has ended, use an 
insulated jumper wire (see page 43) between terminal locations 
12 and 13 for fast reset function.
4.  Interrupt power for 5 seconds. The green indicator light will 
blink 4 times repetitively. Then retry for ignition.
5.  Allow time for any raw gas to dissipate and repeat steps 3 and 
4 until ignition is achieved. 
6.  Turn burner off and install glass door frame assembly.
7.  Test ignition of burner with glass door in place.
NOTE: UNIT MUST BE PROPERLY GROUNDED FOR ELECTRONIC IGNITION TO FUNCTION.
  On initial installation, or after extended periods where the fireplace has not been used, gas lines may require purging.  
  The installer or qualified service person may use the following purge procedures to prevent the delays that would be caused by 
waiting for the lockout periods between tries for ignition.
INSULATED 
JUMPER WIRE
INITIAL START UP GAS LINE PURGE
PURGE PROCEDURE
With proper installation and maintenance, your new Direct Vent Gas Fireplace will provide years of trouble-free service. If you do 
experience a problem, refer to the troubleshooting guide below. This guide will assist a qualified service person in the diagnosis of 
problems and the corrective action to be taken.  Refer to page 44 for initial startup and GAS Line purge instructions.
SYMPTOM
CHECK
ACTION
No spark when system is turned to “ON” 
and reset cycle* has been completed
Check for 120V between black “hot” line 
at  control  module  and  “white”  return  at 
module
If 120V not present, check fuse or circuit 
breaker  or  repair  wiring  leading  to 
fireplace.
Spark for six (6) seconds at ignitor, but no 
ignition of burner. 
a. Check that gas is turned on and system 
purged
Turn gas on and/or purge system
b. Check that tips of ignitor are directly 
above ports on main burner. Spark is 
between  electrodes  and  not  from  one 
electrode to burner.
Position  electrodes  so  tips  are  directly 
above burner port ports and about ¼" to 
3/8" above burner.
c. Check for 120V at each coil on the gas 
valve and listen for click, indicating gas 
valve is opening.
If  120V  present,  but  gas  valve  does  not 
click, replace gas valve.
Spark  for  six  (6)  seconds,  main  burner 
lights, but goes out when spark stops.
Check  for  clean  ground  path  between 
electrode  bracket  and  fireplace  chassis. 
Check  wiring  to  wiring  diagram  label. 
Check for broken electrode on high-tension 
lead attachment to module.
Clean, position according to wiring diagram, 
and repair defective electric connections. If 
all  electrical  connections  are  clean  and 
correct, replace module.
Main burner lights normally and then goes 
out.
a. Check thermostat if applicable.
Turn  thermostat  up  to  call  for  heat  or 
replace
b. Check high-tension lead and connector 
for shorts. 
Replace spark electrode assembly
c.  Refer  to  installation  instructions 
troubleshooting  guide  for  issues  such 
as venting.
Repair as required.
DIRECT IGNITION TROUBLESHOOTING