REQUIREMENTS FOR MASSACHUSETTS
For all side wall horizontally vented gas fueled equipment 
installed  in  every  dwelling,  building  or  structure  used  in 
whole  or  in  part  for  residential  purposes,  including  those 
owned  or  operated  by  the  Commonwealth  and  where  the 
side wall exhaust vent termination is less than seven (7) feet 
above finished grade in the area of the venting, including but 
not limited to decks and porches, the following requirements 
shall be satisfied:
1.  INSTALLATION  OF  CARBON  MONOXIDE 
DETECTORS. At the time of installation of the side wall 
horizontal vented gas fueled equipment, the installing 
plumber  or  gasfitter  shall  observe  that  a  hard  wired 
carbon  monoxide  detector  with  an  alarm  and  battery 
back-up  is  installed  on  the  floor  level  where  the  gas 
equipment is to be installed. In addition, the installing 
plumber or gasfitter shall observe that a battery operated 
or hard wired carbon monoxide detector with an alarm 
is  installed  on  each  additional  level  of  the  dwelling, 
building or structure served by the side wall horizontal 
vented gas fueled equipment. It shall be the responsibility 
of the property owner to secure the services of qualified 
licensed professionals for the installation of hard wired 
carbon monoxide detectors
 
a.  In the event that the side wall horizontally vented 
gas fueled equipment is installed in a crawl space or 
an attic, the hard wired carbon monoxide detector 
with alarm and battery back-up may be installed on 
the next adjacent floor level.
 
b.  In the event that the requirements of this subdivision 
can  not  be  met  at  the  time  of  completion  of 
installation, the owner shall have a period of thirty 
(30) days to comply with the above requirements; 
provided, however, that during said thirty (30) day 
period, a battery operated carbon monoxide detector 
with an alarm shall be installed.
2.  APPROVED  CARBON  MONOXIDE  DETECTORS. 
Each carbon monoxide detector as required in accordance 
with the above provisions shall comply with NFPA 720 
and be ANSI/UL 2034 listed and IAS certified. 
3.  SIGNAGE. A metal or plastic identification plate shall be 
permanently mounted to the exterior of the building at a 
minimum height of eight (8) feet above grade directly in 
line with the exhaust vent terminal for the horizontally 
vented gas fueled heating appliance or equipment. The 
sign shall read, in print size no less than one-half (1/2) 
inch  in  size,  “GAS  VENT  DIRECTLY  BELOW. 
KEEP CLEAR OF ALL OBSTRUCTIONS”.
4.  INSPECTION. The state or local gas inspector of the 
side wall horizontally vented gas fueled equipment shall 
not  approve  the  installation  unless,  upon  inspection, 
the inspector observes carbon monoxide detectors and 
signage installed in accordance with the provisions of 
248 CMR 5.08(2)(a) 1 through 4.
 
(b)  EXEMPTIONS:  The  following  equipment  is 
exempt from 248 CMR 5.08(2)(a)1 through 4: 
 
 
1.  The  equipment  listed  in  Chapter  10  entitled 
“Equipment Not Required To Be Vented” in the 
most current edition of NFPA 54 as adopted by 
the Board; and 
 
 
2.  Product Approved side wall horizontally vented 
gas  fueled  equipment  installed  in  a  room  or 
structure separate from the dwelling, building or 
structure used in whole or in part for residential 
purposes. 
 
(d)  MANUFACTURER  REQUIREMENTS  -  GAS 
EQUIPMENT  VENTING  SYSTEM  NOT 
PROVIDED. When the manufacturer of a Product 
Approved side wall horizontally vented gas fueled 
equipment does not provide the parts for venting the 
flue gases, but identifies “special venting systems”, 
the following requirements shall be satisfied by the 
manufacturer:
 
 
1.  The  referenced  “special  venting  system” 
instructions shall be included with the appliance 
or equipment installation instructions; and
 
 
2.  The “special venting systems” shall be Product 
Approved by the Board, and the instructions for 
that system shall include a parts list and detailed 
installation instruction.
 
(e)  A copy of all installation instructions for all Product 
Approved side wall horizontally vented gas fueled 
equipment,  all  venting  instructions,  all  parts  lists 
for venting instructions, and/or all venting design 
instructions  shall  remain  with  the  appliance  or 
equipment at the completion of the installation.