 HP ProLiant DL360 Generation 4 Server Reference and Troubleshooting Guide 
 
Hot-Plug SCSI Hard Drive LED Combinations 
    
Activity 
LED (1)  
Online 
LED (2) 
Fault LED 
(3) 
Interpretation 
On, off, or 
flashing 
On or off 
Flashing 
A predictive failure alert has been received for this drive. 
Replace the drive as soon as possible. 
 
On, off, or 
flashing 
On 
Off 
The drive is online and is configured as part of an array. 
If the array is configured for fault tolerance and all other drives in the 
array are online, and a predictive failure alert is received or a drive 
capacity upgrade is in progress, you may replace the drive online.
 
On or 
flashing 
Flashing Off 
Do not remove the drive. Removing a drive may terminate the 
current operation and cause data loss. 
The drive is rebuilding or undergoing capacity expansion.
 
On Off Off Do not remove the drive. 
The drive is being accessed, but (1) it is not configured as part of an 
array; (2) it is a replacement drive and rebuild has not yet started; or 
(3) it is spinning up during the POST sequence.
 
Flashing Flashing Flashing Do not remove the drive. Removing a drive may cause data loss 
in non-fault-tolerant configurations. 
Either (1) the drive is part of an array being selected by an array 
configuration utility; (2) Drive Identification has been selected in 
HP SIM; or (3) drive firmware is being updated.
 
Off 
Off 
On 
The drive has failed and has been placed offline. 
You may replace the drive.
 
Off 
Off 
Off 
Either (1) the drive is not configured as part of an array; (2) the drive 
is configured as part of an array, but it is a replacement drive that is 
not being accessed or being rebuilt yet; or (3) the drive is configured 
as an online spare. 
If the drive is connected to an array controller, you may replace the 
drive online.