JKSSS+ Series - 42
JKSSS+ Series   
 
 
 
 
           
            
   2.3 - 4.2KV
5.1.9 RTD Configuration (Setpoint Page 9)
Setpoint
Page
Security
Level
Description
Factory Setting
Default
Range
Section
Use NEMA Temp for RTD Values
Disabled
Enabled or Disabled
SP9.1
# of RTD Used for Stator
4
0-6
SP9.2
RTD Voting
Disabled
Enabled or Disabled
SP9.3
Stator Phase A1 Type
Off
120 OHM NI, 100 OHM NI, 100 OHM PT, 10 
OHM CU
RTD #1 Description
Stator A1
User defined, Up to 15 Characters
Stator Phase A1 Alarm Level
Off
0-240C (32-464F), Off
Stator Phase A1 Trip Level
Off
0-240C (32-464F), Off
Stator Phase A2 Type
Off
Same as Stator Phase A1
RTD #2 Description
Stator A2
User defined, Up to 15 Characters
Stator Phase A2 Alarm
Off
0-240C (32-464F), Off
Stator Phase A2 Trip Level
Off
0-240C (32-464F), Off
Stator Phase B1 Type
Off
Same as Stator Phase A1
RTD #3 Description
Stator B1
User defined, Up to 15 Characters
Stator Phase B1 Alarm Level
Off
0-240C (32-464F), Off
Stator Phase B1 Trip Level
Off
0-240C (32-464F), Off
Stator Phase B2 Type
Off
Same as Stator Phase A1
RTD #4 Description
Stator B2
User defined, Up to 15 Characters
Stator Phase B2 Alarm Level
Off
0-240C (32-464F), Off
Stator Phase B2 Trip Level
Off
0-240C (32-464F), Off
Stator Phase C1 Type
Off
Same as Stator Phase A1
RTD #5 Description
Stator C1
User defined, Up to 15 Characters
Stator Phase C1 Alarm Level
Off
0-240C (32-464F), Off
Stator Phase C1 Trip Level
Off
0-240C (32-464F), Off
Stator Phase C2 Type
Off
Same as Stator Phase A1
RTD #6 Description
Stator C2
User defined, Up to 15 Characters
Stator Phase C2 Alarm Level
Off
0-240C (32-464F), Off
Stator Phase C2 Trip Level
Off
0-240C (32-464F), Off
End Bearing Type
Off
Same as Stator A1
RTD #7 Description
End Bearing
User defined, Up to 15 Characters
End Bearing Alarm Level
Off
0-240C (32-464F), Off
End Bearing Trip Level
Off
0-240C (32-464F), Off
Shaft Bearing Type
Off
Same as Stator Phase A1
RTD #8 Description
Shaft Bearing
User defined, Up to 15 Characters
Shaft Bearing Alarm Level
Off
0-240C (32-464F), Off
Shaft Bearing Trip Level
Off
0-240C (32-464F), Off
RTD #9 Type
Off
Same as Stator Phase A1
RTD #9 Description
User defined
User defined, Up to 15 Characters
RTD #9 Alarm Level
Off
0-240C (32-464F), Off
RTD #9 Trip Level
Off
0-240C (32-464F), Off
Page 
9
RTD Configuratio
n
Level 
3
Password Protection
SP9.4