Справочник Пользователя для Toshiba VF010H05

Скачать
Страница из 106
JKSSS+ Series - 43
JKSSS+ Series   
 
 
 
 
           
            
   2.3 - 4.2KV
5.1.9 RTD Configuration Page 9 Cont’d
5.1.10 Security Set Password Page 10
5.1.11 Communications Page 11
Setpoint
Page
Security
Level
Description
Factory Setting
Default
Range
Section
RTD #10 Type
Off
Same as Stator Phase A1
RTD #10 Description
User defined
User defined, Up to 15 Characters
RTD #10 Alarm Level
Off
0-240C (32-464F), Off
RTD #10 Trip Level
Off
0-240C (32-464F), Off
RTD #11 Type
Off
Same as Stator Phase A1
RTD #11 Description
User defined
User defined, Up to 15 Characters
RTD #11 Alarm Level
Off
0-240C (32-464F), Off
RTD #11 Trip Level
Off
0-240C (32-464F), Off
RTD #12 Type
Off
Same as Stator Phase A1
RTD #12 Description
User defined
User defined, Up to 15 Characters
RTD #12 Alarm Level
Off
0-240C (32-464F), Off
RTD #12 Trip Level
Off
0-240C (32-464F), Off
Page 
9
RTD Configuration
Level 
3
Password Protection
SP9.4
Setpoint
Page
Security
Level
Description
Factory Setting
Default
Range
Section
Set Level 2 Password
100
000 – 999  Three Digits
SP10.1
Set Level 3 Password
1000
0000 – 9999  Four Digits
SP10.2
Page 
10
Level
 
3
Setpoint
Page
Security
Level
Description
Factory Setting
Default
Range
Section
Set Front Baud Rate
9.6 KB/sec
2.4, 4.8, 9.6, 19.2, 38.4 KB/sec
SP11.1
Set Modbus Baud Rate
9.6 KB/sec
2.4, 4.8, 9.6, 19.2, 38.4 KB/sec
SP11.2
Modbus Address Number
247
1 – 247 
SP11.3
Set Access Code
1
1 – 999 
SP11.4
Set Link Baud Rate
38.4 KB/sec
2.4, 4.8, 9.6, 19.2, 38.4 KB/sec
SP11.5
Remote Start/Stop
Disabled
Enabled or Disabled
SP11.6
Page 11
Communiications
Level 
3
Password Protection