JKSSS+ Series - 58
JKSSS+ Series   
 
 
 
 
           
            
   2.3 - 4.2KV
SP.6 User I/O Configuration (Setpoint Page 6)
(Security Level: 2)
SP6.5 User Programmable External Inputs: The 
controller provides up to 4 digital external inputs 
which are individually programmable. A description 
name can be assigned to each individual input for 
easy identification.
 
• 
External Input #1: Factory programmed for TCB 
Trip.
 
•  External Input #2: If used, this setpoint must be 
enabled.
•  Name Ext. Input #2: The user can assign a 
description name to the input to easily identify 
the cause of external trip or alarm. Up to 15 
characters including spaces can be used to assign 
the name.
 
• External Input #2 Type: The external input can 
be set as either a normally open or normally 
closed contact.
 
•  External Input #2 Time Delay: Upon a change in 
contact setting, the unit will wait the programmed 
amount of time before generating an output. If 
no delay is needed, then input 0 seconds. The 
controller will post an event upon seeing a change 
in state.
•  External Input #3: The setup screens and 
setpoints for External Input #3 includes the option 
of being configured for Dual Ramp. In Dual Ramp 
mode, the initial contact setting is the same as the 
START RAMP #1. Upon a change in input contact 
state, the controller will switch over to START 
RAMP #2 and use that setting for start control 
mode. Note: The start RAMP types should only be 
switched while the motor is stopped. In Setpoint 
Page 4 Relay Assignments, do not assign any 
output relay to this function. The controller will 
ship with External input #3 programmed for dual 
ramp. If it is not needed, disable the dual ramp.
 
•  External Input #4: This input screens are for the 
thermostat input and can be enabled or disabled.  
Note: It is recommended that this function remain 
enabled. If the thermostat indicates an over 
temperature condition, the controller will trip the 
motor. 
USER 
PROGRAMMABLE
EXTERNAL 
INPUTS
(Continued)
TCB FAULT
SELECT:  ENABLED
NAME EXT. INPUT #1
TCB FAULT
Options:  Enabled or Disabled
See text for directions
EXTERNAL INPUT #2
SELECT:  DISABLED
NAME EXT INPUT #2
 Options: Enabled or Disabled
See text for directions
DUAL RAMP
SELECT:  DUAL RAMP
NAME EXT INPUT #3
SECOND RAMP
Options: Enabled, Disabled or
              Dual Ramp
See text for directions
THERMOSTAT
SELECT:  ENABLED
NAME EXT INPUT #4
THERMOSTAT
Options:  Enabled or Disabled 
See text for directions
TCB FAULT
TYPE: NORMALLY OPEN
Options: Normally Open or 
               Normally Closed
EXTERNAL INPUT #2
TYPE: NORMALLY OPEN
Options: Normally Open or 
               Normally Closed
DUAL RAMP
TYPE: NORMALLY OPEN
Options: Normally Open or 
               Normally Closed
THERMOSTAT
TYPE: NORMALLY CLOSED
Options: Normally Open or 
               Normally Closed
TCB FAULT
TIME DELAY: 1 SEC.
Range: 0 - 60 SEC
Increments of 1
EXTERNAL INPUT #2
TIME DELAY: 0 SEC.
Range: 0 - 60 SEC.
Increments of 1
DUAL RAMP
TIME DELAY: 0 SEC.
Range: 0 - 60 SEC
Increments of 1
THERMOSTAT
TIME DELAY: 1 SEC.
Range: 0 - 60 SEC.
Increments of 1