Справочник Пользователя для Toshiba VF010H05

Скачать
Страница из 106
JKSSS+ Series - 56
JKSSS+ Series   
 
 
 
 
           
            
   2.3 - 4.2KV
SP.6 User I/O Configuration (Setpoint Page 6)
(Security Level: 2)
MENU
PAGE 6    USER I/O
CONFIGURATION
TACHOMETER SCALE
SELECTION: DISABLED
TACH ACCEL TRIP MODE
SELECT: DISABLED
Options:  ENABLED or
               DISABLED
Options:  UNDERSPEED,
 OVERSPEED or DISABLED
(Hit DOWN ARROW five times)
MANUAL TACH SCALE
4.0 mA: 0 RPM
TACH RAMP TIME
:  20 SEC
MANUAL TACH SCALE
20.0 mA: 2000 RPM
TACH UNDERSPEED TRIP
PT:  1650 RPM
TACH OVERSPEED TRIP
PT:  1850 RPM
ANALOG OUTPUT #1
:RMS CURRENT
ANALOG OUTPUT #1
4ma:  0
ANALOG OUTPUT #2
:% MOTOR LOAD
ANALOG OUTPUT #2
4mA:  0
ENABLED
Range: 1 - 120 SEC., 
              Disabled
Increments of 1
Range: 0 - 3600
Increments of 5
Range: 0 - 3600
Increments of 5
Range:
RPM                         0 - 3600
Hottest Bearing        0 - 200°C
Hottest Stator RTD   0 - 200°C
RMS Current            0 - 6500A
% Motor Load          0 - 1000%
KW 
            0-30000 KW
OFF
Increments of 1
Analog Output
     Range
Range: See Analog Output #1 
Increments of 1
ANALOG OUTPUT #1
20mA:  250
ANALOG OUTPUT #2
20mA:  1000
Range: 0-65535
Increments of 1
TACH ACCEL TRIP
DELAY: 1 SEC
Range: 1 - 60
Increments of 1
Range: 0-3600
Increments of 5
Range: 0-3600
Increments of 5
Range: 0-65535
Increments of 1
Range: 0-65535
Increments of 1
Range: 0-65535
Increments of 1
USER PROGRAMMABLE
EXTERNAL INPUTS
Continued...