BGU Override T3
Set to ‘Yes’ to enable activation of a break glass unit to override any T3 timer.
BGU Override T4
 Set to ‘Yes’ to enable activation of a break glass unit to override any T4 timer.
Table 14: Standard Features – Output Group Information
11.5.1 Fire 
Output
Output Group 512 is reserved for signalling to Fire Output routing equipment. The Fire Output display light turns
on during any fire condition when one or more output type device, loop or panel derived has been assigned to
output group 512. The Fire Output turns off when the panel is Reset. The output does not operate if the class
change input is activated.
11.5.2
Isolate Output Group
Output Group 511 is reserved for signalling the panel isolate status condition to a remote system such as a
BMS or Pager system using an output type module. Output group 511 will activate its associated loop or panel
derived outputs when any part of the system is isolated at access level 2 or 3. The output group will only de-
activate when all isolations are removed from the system.
11.6   
SET ACTIVATIONS
The control panel can be programmed to perform a number of different cause and effect strategies to meet the
system design and installation requirements. In order to perform the evacuation programming, output modules
and sounders connected to the detection loop together with panel output circuits located on the BLC cards, are
attributed to Output Groups. Programming is achieved through the panel software by linking the output groups
to either fire zones, plant zones, or by exception, single loop devices. Output groups can also be linked to other
output groups to perform phased evacuations where the expiry of delay timers T3 & T4 trigger other groups to
start operating.
The most basic evacuation procedure is a common alarm system, where a more complex cause & effect
strategy is required; the preferred and simple method of programming the control panel is using the zone to
output group.
The following examples describe some possible cause & effect strategies,
11.6.1 Common 
Alarm 
Installations
To create a common alarm evacuation & shutdown cause & effect strategy for sounder and relay modules,
Using Loop Device Information, Table 12 and Panel Functions, Table 13 assign all sounder circuits, panel or
loop, to Output Group 1.
Using Loop Device Information set the Group 1 attributes as follows: -
!
 
Enter appropriate text 
= e.g. Common Sounders
!
 
Action = 
common
!
 
Manual Sound 
= Yes
!
 
Clear
= Silence
Using Loop Device Information, Table 12 and Panel Functions, Table 13 assign all relay modules or outputs,
panel or loop, to Output Group 2.
Using Loop Device Information set the Group 2 attributes as follows: -
!
 
Enter appropriate text 
= e.g. Plant Shutdowns
!
 
Action = 
Common
!
 
Manual Sound 
= No
!
 
Clear
= Reset
Note: relay modules & contacts, after a fire condition generally de-activate with a panel reset and do not operate
when the manual Evacuation button is pressed.
No further programming should be necessary.