11.6.2
Zone by Zone Alarm Installations
To create a geographical zone evacuation & shutdown cause / effect strategy,
Using Loop Device Information, Table 12 and Panel Functions, Table 13 assign all sounder circuits located in
zone 1, panel or loop, to Output Group 1.
zone 1, panel or loop, to Output Group 1.
Assign Zone 2 sounders to Output Group 2
Repeat until all sounders are allocated to a separate Output Group.
Repeat until all sounders are allocated to a separate Output Group.
Using Loop Device Information set the Group 1 attributes as follows: -
!
Enter appropriate text
= e.g. Sounders Zone One or Sounders Ground Floor
!
Action =
Program
!
Manual Sound
= Yes
!
Clear
= Silence
Using Loop Device Information, Table 12 and Panel Functions, Table 13 assign all relay modules or outputs
located in Zone 1, panel or loop, to the next available Output Group.
located in Zone 1, panel or loop, to the next available Output Group.
Assign Zone 2 relay modules to next available Output Group.
Repeat until all relay modules are allocated to a separate Output Group.
Repeat until all relay modules are allocated to a separate Output Group.
Using Loop Device Information set the Group attributes as follows: -
!
Enter appropriate text
= e.g. Plant Shutdowns Zone One
!
Action =
program
!
Manual Sound
= No
!
Clear
= Reset
Activations can be programmed from the following locations:
!
Using the panel menu, Activations is located at Set → Standard features → Activations → Zone
followed by the required zone number to be programmed.
followed by the required zone number to be programmed.
!
Using the VIPER software, Set Activations is located at Edit →Standard features → Set Activations
→ Zone to Output Groups.
→ Zone to Output Groups.
Using the control panel, assign zone 1 to operate sounder output group 1 using the programming style ‘Evac’
Assign zone 2 to operate sounder output group 2. Repeat for the remainder of the sounder groups followed by
the relay module output groups.
Assign zone 2 to operate sounder output group 2. Repeat for the remainder of the sounder groups followed by
the relay module output groups.
Using VIPER software, assign zone 1 to evacuate output group 1 using the evacuation style symbol, capital ‘E’
as shown in Figure 31 and repeat for the remaining zones.
as shown in Figure 31 and repeat for the remaining zones.
Figure 31: Example VIPER – Set Activations – Zones to Output Groups