11.6.2 
Zone by Zone Alarm Installations
To create a geographical zone evacuation & shutdown cause / effect strategy,
Using Loop Device Information, Table 12 and Panel Functions, Table 13 assign all sounder circuits located in
zone 1
, panel or loop, to Output Group 1.
Assign Zone 2 sounders to Output Group 2
Repeat until all sounders are allocated to a separate Output Group.
Using Loop Device Information set the Group 1 attributes as follows: -
!
 
Enter appropriate text 
= e.g. Sounders Zone One or Sounders Ground Floor
!
 
Action = 
Program
!
 
Manual Sound 
= Yes
!
 
Clear
= Silence
Using Loop Device Information, Table 12 and Panel Functions, Table 13 assign all relay modules or outputs
located in Zone 1
, panel or loop, to the next available Output Group.
Assign Zone 2 relay modules to next available Output Group.
Repeat until all relay modules are allocated to a separate Output Group.
Using Loop Device Information set the Group attributes as follows: -
!
 
Enter appropriate text 
= e.g. Plant Shutdowns Zone One
!
 
Action = 
program
!
 
Manual Sound 
= No
!
 
Clear
= Reset
Activations can be programmed from the following locations:
!
 
Using the panel menu, Activations is located at Set  → Standard features → Activations → Zone
followed by the required zone number to be programmed.
!
 
Using the VIPER software, Set Activations is located at Edit →Standard features → Set Activations
→ Zone to Output Groups.
Using the control panel, assign zone 1 to operate sounder output group 1 using the programming style ‘Evac’
Assign zone 2 to operate sounder output group 2. Repeat for the remainder of the sounder groups followed by
the relay module output groups.
Using VIPER software, assign zone 1 to evacuate output group 1 using the evacuation style symbol, capital ‘E’
as shown in Figure 31 and repeat for the remaining zones.
Figure 31: Example VIPER – Set Activations – Zones to Output Groups