The various timers when used in conjunction with the fire zones and output groups can create a number of
different cause & effect strategies. The example shown in Figure 33 provides the following: -
Zone of origin to provide Alarm Accept (T1) delay of 1 minute
Investigation (T2) time of 3 minutes
Adjacent Zones delayed for a further 2 minutes (T3)
Adjacent Zones to Alert (pulsing) for further 2 minutes (T4)
Constant alarm to follow upon completion of the Alert delay
Note: Operation of a Break Glass or the Delay Override button will override T2.
Figure 33: Zone to Group Timers
11.6.5
Single Device to Output Group Programming
Single Device to Output Group programming effectively removes the device from the zone voting allowing the
activation of the individual device to trigger different output groups. To programme Single Device to Output
Groups the device must first be removed from its zone voting, set the Program by option to Device using
VIPER. Refer Table 12.
Activations can be programmed from the following locations:
!
 
Using the panel menu, Activations is located at Set → Standard features → Activations → Device
followed by the required device address number to be programmed.
!
 
Using the VIPER software, Set Activations is located at Edit →Standard features → Set Activations
→ Device to Output Groups.
Select the output group number to be programmed, style of activation and enter the device address parameters
to activate the output group.
11.6.6
Plant Alarm to Output Group Programming
Output Groups can also be programmed to respond to the activation non-fire related devices assigned to Plant
Alarm zones.
Plant Alarms can be programmed from the following locations:
!
 
Using the panel menu, Activations is located at Set  → Standard features → Activations → Plant
followed by the required device address number to be programmed.
!
 
Using the VIPER software, Set Activations is located at Edit →Standard features → Set Activations
→ Plant Alarms to Output Groups.