Power, electrical, and controls  24 
Capacities 
HP POD 40c G2 capacity limitations 
The capacity limitations for the HP POD 40c G2 are separated into two categories: electrical power and 
mechanical cooling capacities. Both of these categories are interdependent and must be considered in 
conjunction with the overall customer requirements. 
 
Electrical and mechanical cooling capacities 
 
Feature 
Specification 
Critical IT electrical 
connections 
2 x 800A feeders at 415Y/240 V, 3-phase, 4-wire, 
with equipment ground conductors 
10.2 x 10.2 cm (4 x 4 in) conduit fittings per feeder 
provided 
Critical IT power 
capacity 
2N Redundant—576 kW 
Mechanical cooling 
electrical connections 
Not applicable 
Power for the cooling system fans comes from house 
power. 
Mechanical cooling 
capacity 
 
N+1 Redundant—400 kW 
 
Non-redundant—600 kW 
 
 
Power feeders 
  
 
IMPORTANT:
  A licensed electrician must connect the power according to all local and national 
electrical codes, and must comply with manufacturer specifications. 
  
The HP POD 40c G2 has eight power feeder couplings that provide the entrance for power to the POD. The 
power feeders route into the top of each electrical panel on the end of the HP POD 40c G2.