HP Performance Optimized Data Center (POD) 40c User Manual
Power, electrical, and controls 24
Capacities
HP POD 40c G2 capacity limitations
The capacity limitations for the HP POD 40c G2 are separated into two categories: electrical power and
mechanical cooling capacities. Both of these categories are interdependent and must be considered in
conjunction with the overall customer requirements.
conjunction with the overall customer requirements.
Electrical and mechanical cooling capacities
Feature
Specification
Critical IT electrical
connections
2 x 800A feeders at 415Y/240 V, 3-phase, 4-wire,
with equipment ground conductors
10.2 x 10.2 cm (4 x 4 in) conduit fittings per feeder
provided
provided
Critical IT power
capacity
2N Redundant—576 kW
Mechanical cooling
electrical connections
electrical connections
Not applicable
Power for the cooling system fans comes from house
power.
power.
Mechanical cooling
capacity
capacity
•
N+1 Redundant—400 kW
•
Non-redundant—600 kW
Power feeders
IMPORTANT:
A licensed electrician must connect the power according to all local and national
electrical codes, and must comply with manufacturer specifications.
The HP POD 40c G2 has eight power feeder couplings that provide the entrance for power to the POD. The
power feeders route into the top of each electrical panel on the end of the HP POD 40c G2.
power feeders route into the top of each electrical panel on the end of the HP POD 40c G2.