Environmental control system  54 
 
CAUTION: 
 Making changes to the ECS in the service-level area can cause the cooling system 
components to fail. Only allow authorized, qualified, and trained personnel to change 
configuration settings in the service-level area of the ECS. 
  
You must select Save to store the parameter changes in the system configuration file. If you do not save your 
changes, the old parameters stored in the configuration file reload when the system starts. 
 
Item 
Description 
Control routine interval 
Sets the interval within seconds when the control routine is activated 
Set point 
temperature/pressure 
Sets the temperature and pressure setpoints 
Temperature and pressure 
time constant 
Used by the low pass filter to even the measurement values out 
P,I, and D gain 
Proportional, integral, and differential gains influence the rate of change in the 
position of the flow control valve or the fan speed in order to reach the 
pre-determined setpoints. 
 
 
ECS alarms 
The alarms pertaining to the health of the HP POD 40c G2 and its components are relayed through the ECS. 
  
Alarm 
Meaning 
Solution 
Fan failure 
One of the fans is not working.  See the HP Performance Optimized Datacenter 
40c G2 Maintenance and Service Guide or 
contact HP service if you are still within your 
service contract. 
Sensor failure 
One of the sensors is not 
working. 
See the HP Performance Optimized Datacenter 
40c G2 Maintenance and Service Guide
 or 
contact HP service if you are still within your 
service contract. 
Leak detection 
The drain pan sensor detects 
water in the pan. 
See the HP Performance Optimized Datacenter 
40c G2 Maintenance and Service Guide
 or 
contact HP service if you are still within your 
service contract. 
Change filter 
The return air filters are full. 
Replace the return air filters. For more 
information, see the HP Performance Optimized 
Datacenter 40c G2 Maintenance and Service 
Guide
High temperature 
The cold aisle temperature has 
surpassed the setpoint 
temperature. 
Verify that you have water flowing into your 
HP POD 40c G2 and the fans are 
operating. 
Contact HP service if you are still within your 
service contract. 
 
Low temperature 
The cold aisle temperature is 
too low. 
Verify that all components are operating 
normally. 
Contact HP service if you are still within your 
service contract.