Справочник Пользователя для HP Performance Optimized Data Center (POD) 40c

Скачать
Страница из 84
 
Environmental control system  55 
Alarm 
Meaning 
Solution 
EPO 
The EPO system activates and 
the HP POD 40c G2 shut 
down. 
Follow the emergency procedures for your 
facility. 
After the emergency is cleared, reset the 
EPO and other HP POD 40c G2 systems. 
 
Differential pressure 
The difference in pressure 
between the hot and cold aisles 
is above the setpoints. 
Verify that the cold/hot aisle differential 
pressures are within the setpoints. 
Contact HP service if you are still within your 
service contract. 
 
 
 
Safety and security alarms 
Alarms pertaining to the safety of the HP POD 40c G2 are (optionally) relayed through your building fire and 
security dispatch. 
  
Alarm 
Meaning 
Solution 
Fire alarm* 
The HP POD 40c G2 detected a fire.  Activate the EPO. Follow the emergency 
procedures for your facility. 
Security alarm 
(optional) 
A security breach occurred. 
Follow the emergency procedures for your 
facility. 
EPO 
The EPO system activated and the HP 
POD 40c G2 shut down. 
Follow the emergency procedures for your 
facility. 
 
*The fire alarm is relayed to your building fire and security dispatch only if you have connected your facility to the fire 
box (on page 
). 
 
Fire alarm sequence of operations 
If a fire alarm is activated by the VESDA system, the HP POD 40c G2 does the following: 
1. 
Sends an alarm signal to the building fire and security dispatch if you have connected your facility to the 
fire box (on page 
) 
2. 
Activates the fire strobes and horns, starting the 30-second evacuation alarm 
3. 
Releases the suppression agent after a 30-second delay if the optional fire suppression system is 
installed 
  
 
IMPORTANT:
  To interrupt the fire suppression delay for another 30 seconds, press one of the 
abort buttons located next to each personnel door. 
  
If a fire alarm is activated by a manual fire pull, the HP POD 40c G2 does the following: 
1. 
Sends an alarm signal to the building fire and security dispatch if you have connected your facility to the 
fire box (on page 
) 
2. 
Activates the fire strobes and horns, starting the 30-second evacuation alarm 
3. 
Releases the suppression agent after a 30-second delay if the optional fire suppression system is 
installed