Справочник Пользователя для HP Performance Optimized Data Center (POD) 20cp
Power, electrical, and controls 33
Feature
Specification
Rack type
HP POD rack
Max number of racks
10
Max U space per rack
50U
Max U space per HP POD 20c
500U
Server capacity
288 kW power capacity
Average capacity per rack
28.8 kW
Peak capacity per rack
69 kW
Voltage to rack
200-240 VAC
Rack configuration
Redundant/Non-redundant
capabilities
Total number of PDU's
20 (two per rack)
Max power per PDU
30 A = 17 kW; 60 A = 34 kW
Max load (Chilled POD cooling mode)
*
288 kW
Airflow per rack (Chiller POD cooling
mode)
1,700 CFM
*
Dependent on configuration
HP POD 20c lighting
The HP POD 20c includes six LED lights. Three lights are located in the cold aisle and three lights are located
in the hot aisle.
The main light switch is located on the ECS control panel door. For more information on the light switch
in the hot aisle.
The main light switch is located on the ECS control panel door. For more information on the light switch
)."
Two of the six lights are connected to battery backup power, keeping the interior of the HP POD 20c
illuminated during a power outage or emergency.
For more information on lighting, see the HP Performance Optimized Datacenter 20c Maintenance and
illuminated during a power outage or emergency.
For more information on lighting, see the HP Performance Optimized Datacenter 20c Maintenance and
Service Guide.