Справочник Пользователя для Honeywell Home Theater Server T755U

Скачать
Страница из 40
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
13
62-0255—09
Program, Schedule, and Summary 
Menus
To access these menus from the home screen, press the 
MENU button. See Fig. 23.
 
Fig. 23.  Menus.
Depending on whether scheduling is enabled or not, the 
LCD displays one of two menus as shown in Fig. 23. 
Scheduling is enabled from the Setup menu’s Output 
Setup Menu
To access the Setup menu, press and hold the MENU 
button for five seconds. See Fig. 24.
Fig. 24. Setup Menu.
Using the Menus
When you are working with the menus, use the:
• Left arrow button (t) to scroll backward through the 
menus
• Right arrow button (u) to select the highlighted menu 
item and display its content
• Up and Down arrow buttons (p and q) to scroll up and 
down through a list of items or to increase or decrease 
the value of a displayed parameter
NOTES:
1.
If you press the 
HOME button or there is no 
keypad activity for four minutes, you exit 
Program mode and return to the home 
screen.
2.
If you press the 
MENU button, you exit and 
return to the menu.
PROGRAMMING OVERVIEW
The controller must be programmed before being placed 
into service.
IMPORTANT
During programming, the controller is live at all 
times. For example, the contacts may open and 
close when adjusting the setpoint.
The Programming process uses a hierarchical menu 
structure that is easy to use. You press the t and u arrow 
buttons to move forward and backward through the 
menus. 
NOTES:
1.
The T775U controller interface is intuitive. You 
may find that you do not need the following 
procedure instructions to program the control-
ler. You may want to use this procedure sim-
ply as a reference to locate the particular 
option or parameter of interest.
2.
The menus can display only those relays that 
are defined in Setup (see “1.3.2. NBR OF 
RELAYS” on page 22). For example, if you 
configure only one relay, then only one relay 
displays on the appropriate menus.
3.
If you press the 
HOME button or there is no 
keypad activity for four minutes, you exit Pro-
gram mode and return to the home screen.
4.
If you press the 
MENU button, you exit 
Program mode and return to the menu.
Setpoint and Differential
The following describes the relationship between setpoint 
and differential for heating and cooling. These settings are 
programmed for each output relay.
In heating mode, reverse acting mode, and humidify 
mode,  the differential falls below the setpoint. The relay 
de-energizes when the temperature rises to the setpoint. 
As the temperature drops to the setpoint minus the 
differential, the relay energizes.
In cooling mode, direct acting mode, and dehumidify 
mode,  the differential falls above the setpoint. The relay 
de-energizes when the temperature falls to the setpoint. 
As the temperature rises to the setpoint plus the 
differential, the relay energizes. 
Setpoint High Limit
You can set an irreversible setpoint high limit maximum 
value for any single displayed setpoint value.
Adjust the setpoint (at any output) to the desired 
maximum setpoint. Then, simultaneously press the 
HOME, t, and u buttons and continue to press all three 
buttons for five seconds to set the setpoint high limit 
maximum to this value.
NOTE: You must press all three buttons at exactly 
the same time for this action to occur.
MENU
PROGRAM
EXIT
home
menu
OR
MENU DISPLAY WHEN
SCHEDULING IS NOT SET
MENU DISPLAY WHEN
SCHEDULING IS SET
MENU
MOD1             40%
MOD2             60%
DI ON
           HOME
RELAYS  1  2
        ON
F
F
    
SENSORS
SENSOR A
      78
SENSOR B
      84
PROGRAM
SCHEDULE
SUMMARY
EXIT
M24565
home
menu
SETUP
MOD1             40%
MOD2             60%
DI ON
           HOME
RELAYS  1  2
        ON
FIVE
SECONDS
F
F
    
SENSORS
SENSOR A
      78
SENSOR B
      84
SENSORS
OUTPUTS
EXIT
M24566