T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
62-0255—09
14
IMPORTANT
1. This action sets the maximum setpoint value of 
all outputs to the setpoint high limit maximum.
2. Setting the high limit setpoint maximum is 
irre-
versible. If you perform the action inadvertently 
and this setpoint adversely affects the control of 
your system, you must replace the controller.
Programming the T775U 
Controller
To program the controller, perform the setup configuration 
(see “1. Setup”) and then select one of the following 
procedures depending on whether the Reset function is to 
be used:
• Program the Outputs for No Reset — see 
• Program the Outputs for Reset — see 
When programming is complete, you may continue with 
1. SETUP 
Setup provides the ability to change the factory default 
settings for the temperature sensors and outputs, to 
enable/disable reset control, and to enable/disable 
scheduling.
NOTE:
1.
The T775U controller interface is intuitive. You 
may find that you do not need the following 
setup instructions for the sensors and out-
puts. You may want to use this procedure sim-
ply as a reference to locate the particular 
option or parameter of interest.
2.
If you press the 
HOME button or there is no 
keypad activity for four minutes, you exit 
Setup mode and return to the home screen.
3.
If you press the 
MENU button, you exit Setup 
mode and return to the menu.
Once in Setup mode, you use the — 
• Left arrow button (t) to scroll backward through the 
Setup menus
• Right arrow button (u) to select the highlighted menu 
item and display its content
• Up and Down arrow buttons (p and q) to scroll up and 
down through a list of items or to increase or decrease 
the value of a displayed setup parameter