5. INSTALLATION CONSIDERATIONS
LOCATION
The Well-X1
 is designed for indoor and outdoor installations. The NEMA 3R enclosure can be installed 
in direct weather. If installed outdoors, be sure the following conditions are met:
•  Do not install where ambient temperatures can drop below freezing 
or exceed 120° F.
•  Ensure  a  Tuf  Kote
  model  is  selected  (Example:  WX1-302TK) 
for  outdoor  installations.  This  proprietary  coating  is  specifically 
designed to withstand outdoor applications.
•  Use water-tight: wiring conduit, wire nuts and conduit connections 
as dictated by applicable codes and ordinances.
•  Protect the piping from mechanical damage.
•  Install the relief valve blow down tube where venting water will not 
cause personal injury or damage the surrounding property.
•  Drip  Pan  and  Drain:  To  avoid  leaking  and/or  property  damage, 
install  with  a  drip  pan  connected  to  an  adequate  working  drain 
kept clear at all times.
ORIENTATION
Ensure  the  installation  meets  all  applicable  local  codes  and  is  installed  by  a  qualified  professional. 
Additionally, the following should be noted.
•  This unit is designed for vertical installation above ground only. 
Do  not  install  horizontally  or  directly  bury  the  unit.  The  Well-
X1
 may be installed below grade in a well pit or other suitable 
enclosure.  Do  not  locate  in  an  area  where  leaking  or  flooding 
could cause property damage to surrounding areas.
•  Check codes to determine if there are any height requirements 
pertaining  to  the  Well-X1
 
Particularly,  ensure  the  bottom 
drain meets these requirements. If restrictions are imposed on 
the proximity of drain connections to the floor, the unit may be 
elevated  on  blocks  or  the  bottom  drain  tube  can  be  removed 
and plugged, after which a sampling tap may be installed in the 
water lines near the top of the Well-X1
.