Справочник Пользователя для Advantech Barcode Reader RS-485

Скачать
Страница из 348
6-90
ADAM-5000
Command Set
6.8  Analog Output Command Set
Command Syntax
Command Name
Description
$aaSiCjArrff
Configuration
Sets the output range, data
format and slew rate for a
specified channel in a
specified analog output
module in a specified
system.
$aaSiCjB
Configuration Status
Returns the configuration
parameters of a specified
channel in a specified analog
output module of a specified
system.
#aaSiCj(data)
Analog Data Out
Sends a digital value from
the host computer to a
specified channel of a
specified slot in a specified
ADAM-5000 system for
output as an analog signal.
$aaSiCj4
Start-Up Output
Current/Voltage
Configuration
Stores a default output value
in a specified channel. The
output value will take effect
upon startup or reset.
$aaSiCj0
4 mA Calibration
Directs the specified channel
to store parameters following
a calibration for 4 mA output
$aaSiCj1
20 mA Calibration
Directs the specified channel
to store parameters following
a calibration for 20 mA
output
$aaSiCj3hh
Trim Calibration
Trims the specified channel a
specified number of units up
or down
$aaSiCj6
Last Value Readback Returns either the last value
sent to the specified channel
by  a #aaSiCj(data)
command, or start-up output
current/voltage.
5024 Analog Output