Справочник Пользователя для Advantech Barcode Reader RS-485

Скачать
Страница из 348
ADAM-5000
               B-7
Appendix B
B.3
Analog Input Ranges of ADAM-5017H
Note:
The full scale values in this table are theoretical
values for your reference; actual values will vary.
Range
Code
Input
Range
Data
Formats
+Full
Scale
Zero -Full Scale Displayed
Resolution
00h
±10 V
Engineering 11
0
-11
2.7 mV
Two's Comp 0FFF
0
EFFF
1
01h
0-10 V
Engineering 11
0
Don't care 2.7 mV
Two's Comp 0FFF
0
Don't care 1
02h
±5 V
Engineering 5.5
0
-5.5
1.3 mV
Two's Comp 0FFF
0
EFFF
1
03h
0-5 V
Engineering 5.5
0
Don't care 1.3 mV
Two's Comp 0FFF
0
Don't care 1
04h
±2.5 V
Engineering 2.75
0
-2.75
0.67 mV
Two's Comp 0FFF
0
EFFF
1
05h
0-2.5 V
Engineering 2.75
0
Don't care 0.67 mV
Two's Comp 0FFF
0
Don't care 1
06h
±1 V
Engineering 1.375
0
-1.375
0.34 mV
Two's Comp 0FFF
0
EFFF
1
07h
0-1 V
Engineering 1.375
0
Don't care 0.34 mV
Two's Comp 0FFF
0
Don't care 1
08h
±500 mV Engineering 687.5
0
-687.5
0.16 mV
Two's Comp 0FFF
0
EFFF
1
09h
0-500 mV Engineering 687.5
0
Don't care 0.16 mV
Two's Comp 0FFF
0
Don't care 1
0ah
4-20 mA
Engineering 22
4.0
Don't care 5.3 µA
Two's Comp 0FFF
02E9 Don't care 1
0bh
0-20 mA
Engineering 22
0
Don't care 5.3 µA
Two's Comp 0FFF
0
Don't care 1