B-8
ADAM-5000
Data Formats and I/O Ranges
B.4
Analog Output Formats
You can configure ADAM analog output modules to receive data from
the host in Engineering Units.
Engineering Units
Data can be represented in engineering units by setting bits 0 and 1 of
the data format/checksum/integration time parameter to 0.
This format presents data in natural units, such as milliamps.  The
Engineering  Units format is readily parsed by the majority of computer
languages as the total data string length is fixed at six characters:  two
decimal digits, a decimal point and three decimal digits.  The resolution
is 5  µA.
Example:
Channel 1 of the analog output module in slot 0 of an ADAM-5000
system at address 01h is configured for a 0 to 20 mA range.  If the
output value +4.762 mA is desired, the format of the Analog Data Out
command would be #01S0C14.762<cr>
B.5
Analog Output Ranges
Range
Code
(hex)
Output Range
Description
Data Formats Maximum
Specified
Signal
Minimum
Specified
Signal
Displayed
Resolution
30h
0 to 20 mA
Engineering
Units
20.000
00.000
5
 µ
A
% of Span
+100.00
+000.00
5
 µ
A
Hexadecimal
Binary
FFF
000
5
 µ
A
31h
4 to 20 mA
Engineering
Units
20.000
04.000
5
 µ
A
% of Span
+100.00
+000.00
5
 µ
A
Hexadecimal
Binary
FFF
000
5
 µ
A
32h
0 to 10 V
Engineering
Units
10.000
00.000
2.442 mV
% of Span
+100.00
+000.00
2.442 mV
Hexadecimal
Binary
FFF
000
2.442 mV