Use these instructions to install the FPE-1000-SLC Signaling Line Circuit in 
FPA-1000 Analog Addressable Fire Panels.
1.
Install, test, and maintain the FPE-1000-SLC according to these 
instructions, NFPA 72, local codes, and the Authority Having 
Jurisdiction (AHJ).
2.
Follow the procedures in this document to avoid personal injury and 
damage to the equipment. Failure to follow these procedures can cause 
the FPE-1000-SLC to not operate properly. Bosch is not responsible for 
improperly installed, tested, or maintained devices.
3.
Failure to follow the mounting instructions in this document can 
damage the fire panel.
4.
Refer to the FPA-1000 Installation and Operation Guide 
(P/N F.01U.173.607) for detailed wiring style requirements and 
complete programming instructions.
Installation
The mainboard allows for the installation of two FPE-1000-SLC Signaling 
Line Circuits. The first FPE-1000-SLC is mandatory equipment at the top 
position on the mainboard. A second FPE-1000-SLC plug-in module can be 
installed as an option in the position below the first SLC board. The bottom 
position can be equipped with an optional FPE-1000-CITY City Tie Plug-in 
Module. 
The FPE-1000-SLC Signaling Line Circuits connect directly to the mainboard, 
and are detected and supervised automatically when power is applied to the 
control panel.
1.
Bring the plug-in module into position with the horizontal terminal 
lettering facing the front side of the control panel. Slide the plug-in 
CAUTION! 
Electrostatic discharge! 
Ground yourself using a wrist strap or take other suitable 
actions.
The FPA-1000 mainboard and FPE-1000-SLC plug-in module 
have static-sensitive componentsthat could become damaged. 
Run the ground wire to the enclosure before handling the 
mainboard or plug-in modules. Touch ground before unpacking 
and handling the mainboard or plug-in modules. This discharges 
any static electricity in your body. Continue touching the 
enclosure while installing the mainboard or plug-in modules.
DANGER! 
Before installing the FPE-1000-SLC plug-in module, remove all 
AC and battery power from the fire panel.