Observe maximum circuit resistance of 50 Ω.
For Class B, the total wire length of all branches connected to one 
FPE-1000-SLC module (terminals S1+/SC1- and S2+/SC2-) must not exceed 
30,000 feet (9140 m).
The maximum distance an analog addressable detector or module is allowed 
to be located from the control panel (for Class A and Class B SLC) is limited 
depending on the wire gauge; refer to Table 1.
Table 1
Maximum Wiring Distance for SLC Circuits
Measuring Circuit Resistance
1.
Remove the field wiring from the SLC terminals and short either the 
return wire in Class A (Figure 2, Page 4, left side, Item 1 Class A) or 
short the end of the farthest device in Class B (Figure 2, Page 4, right 
side, Item 1 Class B) using clip leads.
2.
Read the total resistance of all wires associated with the circuit 
(Figure 2, Page 4, both sides, item 2). The maximum circuit resistance is 
50 Ω.
Wiring Styles
NOTICE! 
 Wire distances are computed using copper wire. When using 
twisted pair or sheilded wire, observe the maximum circuit 
specifications.
Wire Gauge 
Maximum Wiring Distance (for Class A and 
Class B SLC)
12 AWG (3.3 mm
2
)
10,000 feet (3050 m)
14 AWG (2.1 mm
2
)
10,000 feet (3050 m)
16 AWG (1.3 mm
2
)
6200 feet (1890 m)
18 AWG (0.8 mm
2
)
3900 feet (1190 m)
SLC 
Terminal
Specification Class A Style 6 and 7 
(refer to Figure 3, Page 4
, left side)
S1+ | SC1-
Terminals used for outgoing loop Class A wiring
S2+ | SC2-
Terminals used for return loop Class A wiring
SLC 
Terminal
Specification Class B Style 4 
(refer to Figure 3, Page 4
, right side)
S1+ | SC1-
Terminals used for first stub Class B wiring