INSTALLER/CONFIGURATION MENU
1)  This control can be confi gured for:
 
MS 2 – Multi-Stage System (no heat pump)
 
HP 1 – Heat Pump with one stage of compressor
 
HP 2 – Heat Pump with two stage compressor or two
 
compressor system, Gas or Electric backup
 
SS 1 – Single Stage System
2)  GAS or Electric (ELE) fan operation. If the heating sys-
tem  requires the thermostat to energize the fan, select 
ELE. Select GAS if the heating system energizes the fan 
on a call for heat.
3)  Select Cool Savings™ value – Selects the amount 
of adjustment for the Cool Savings™ feature in Cool 
mode with 1 (1°) being the least amount of adjustment 
and 6 (6°) being the most amount of adjustment. Default 
value is 0 which disables this feature. Cool Savings is 
an optional energy saving feature that can reduce your 
cooling costs. It is based on the principal that lower 
indoor humidity makes a slightly higher temperature 
feel more comfortable. Cool Savings operates during 
periods of high demand which normally occur on the 
hottest summer days when a cooling system may run 
for hours to reach the thermostat setting. Long cooling 
run times also lower the indoor humidity. Cool Savings, 
very slowly, adjusts the setpoint temperature to make the 
setpoint closer to the displayed room temperature, to a 
maximum of the number of degrees you select. Adjust-
ing the setpoint temperature over a long cooling run time 
allows the system to reach your set temperature and turn 
off. The room temperature will actually be higher than 
the thermostat displays but the reduction in humidity will 
allow comfort at the slightly higher temperature.
 
To turn this feature on in the Cool mode press Cool  
Savings. 
The display will show “Save” next to the 
setpoint temperature. When Cool Savings is making ad-
justments to the room temperature display “Save” will be 
fl ashing and the displayed room temperature may vary 
within the adjustment range you selected. 
 If 
“Save” is not displayed and this feature is OFF, no 
change will occur when the cooling system is continu-
ously running during periods of high demand.
4)  Energy Management Recovery: (this step is skipped if
 
confi gured to be non-programmable). Energy Manage-
ment Recovery (E) On enables the thermostat to start 
heating or cooling early to make the building temperature 
reach the program setpoint at the time you specify. Heat-
ing will start 5 minutes early for every 1° of temperature 
required to reach setpoint.
 
Example: E On is selected and your heating is pro- 
grammed to 65° at night and 70° at 7 AM. If the build-
ing temperature is 65°, the difference between 65° and 
70° is 5°. Allowing 5 minutes per degree, the thermostat 
setpoint will change to 70° at 6:35 AM. Cooling allows 
more time per degree, because it takes longer to reach 
set temperature.
5, 6 & 7) Cycle Rate Selection – The factory default setting 
for Heat and Cool modes, SS1, MS2, is medium cycle 
(ME). For Heat Pump, HP1, HP2, the default setting is 
medium (ME). For Emer (Aux) the default setting is fast 
cycle (FA). 
To change cycle rate, press the 
 or 
 
key.
 
Cycle rate differentials for different settings are:
 
 
   Fast 
Medium 
Slow
 
MODE 
 
  FA 
ME 
SL
 
 
Heat  (SS1, MS2)  
0.4°F 
0.6°F 
1.7°F
 
 
Cool  (SS1, MS2)  
0.9°F 
1.2°F 
1.7°F
 
 
Heat Pump (HP1, HP2) 
0.9°F 
1.2°F 
1.7°F
 
 
Emer (HP1, HP2)  
0.6°F 
  - 
1.7°F
8)  Select Compressor Lockout CL OFF or ON – Select-
ing CL ON will cause the thermostat to wait 5 minutes 
between cooling cycles. This is intended to help protect 
the compressor from short cycling. Some newer com-
pressors already have a time delay built in and do not 
require this feature. Your compressor manufacturer can 
tell you if the lockout feature is already present in their 
system. When the thermostat compressor time delay oc-
curs, it will fl ash the setpoint for up to fi ve minutes.
9)   System Mode Confi guration – This thermostat is con-
fi gured for Heat and Cool (SYSTEM switch with Cool Off  
Heat) default. It can also be confi gured for Heat and Cool  
with Auto changeover (Heat, Auto, Cool, Off), Heat only 
 
with fan (Off Heat), Heat only without fan, Auto only  
(Auto Off), and Cool only (Cool Off).
10)  Select Backlight Display – The display backlight im-
proves display contrast in low lighting conditions. When 
the “C” terminal is powered, selecting backlight CdL ON 
will keep the light on continuously. Select backlight OFF 
will turn the light on momentarily after any key is pressed. 
When the “C” terminal is not powered, the light will be on 
momentarily  after any key is pressed no matter whether 
the backlight is selected ON or OFF.
11)  Select Temperature Display Adjustment 4 LO to 4 HI 
– Allows you to adjust the room temperature display up 
to 4° higher or lower. Your thermostat was accurately cali-
brated at the factory, but you have the option to change 
the display temperature to match your previous thermo-
stat. The current or adjusted room temperature will be 
displayed.
12)  Select F° or C° Readout – Changes the display readout
 
to Celsius or Fahrenheit as required.
13)  Limited Heat Range – This feature provides a maximum 
setpoint temperature for heat. The default setting is 90°F. 
It can be changed between 62°F and 89°F by pressing 
the 
 or 
 key.
14)  Limited Cool Range – This feature provide a minimum 
setpoint temperature for cool. The default setting is 45°F. 
It can be changed between 46°F and 82°F by pressing 
the 
 or 
 key.
15)  Program Options: 1F85 only, confi gured for 5/1/1 day or 
 
5/2 day programming or non-programming mode. The 
default setting is P2, indicating 5/2 day programming. 
The programs per week can be toggled to P3 or P0 by 
pressing the 
 or 
 keys. A selection of 0 Days for 
non-programmable will eliminate the need for EMR, and 
that step in the menu will be skipped.
16 & 17) Select Automatic Schedule – 1F85 only, with just  
one touch of the Auto Schedule key this feature allows
 
you to program a desired comfort temperature into all the
 
program periods along with a 6° set back for night peri-
ods of both Heat and Cool programs. Factory default is 
“On” for both. When Heat AS On and Cool AS On are 
activated while in Heat or Cool mode, select desired 
setpoint temperature and press Auto Schedule. This 
value will be copied into all the morning, day and evening 
program periods. The night program periods will have a 
6°F set back.
18 & 19) Select Fast Second Stage ON or OFF – Heat 
pump or Multi-stage only, in the run mode, with the fast 
Heat feature enabled (FA Heat On), if the Heat setpoint 
temperature is manually raised by 3°F (2°C) or more 
above the actual temperature using 
 the second 
stage will energize immediately. With FA OFF, second 
stage will not energize until the setpoint temperature is 
1°F or more above actual temperature for more than ten 
minutes. The Fast Cool feature (FA Cool) provides the 
same controls when the setpoint temperature is lowered.
20)  Select Daylight Saving Time Calculation – 1F85 only,
 
this feature will allow the thermostat to calculate the DST 
 
automatically and apply it to the Real Time Clock display. 
 
Default On. Use 
 or 
 touch keys to select the
 feature 
OFF.