Once the thermostat is installed, it should be thoroughly tested.  
caution!:  
Do not energize the air conditioning system when the outdoor temperature is below 50 
degrees. It can result in equipment damage or personal injury.
Cool Test
1. Slide Mode switch to Cool mode.  
2.  Adjust set temperature so it is 5 degrees below room temperature. 
3.  Air conditioning should come on within a few seconds. Status indicator may come on.
4.  Adjust the set temperature 2 degrees above the room temperature and the A/C should turn off.  
There may be a fan delay on your system.
 
  Note:  There is a fi ve minute time delay to protect the compressor after it turns off. To 
temporarily bypass the fi ve minute delay, slide the Mode switch to OFF for 2 seconds 
and then back to Cool.
Heat Test
1. Slide Mode switch to Heat mode. 
2.  Adjust the set temperature so it is 5 degrees above the room temperature.
3.  Heat should come on within a few seconds. Status indicator may come on.   
4.  Adjust the set temperature so it is 2 degrees below the room 
temperature and the heat should turn off.  There may be a fan delay on your system.
 
  Note:  For heat pumps, there is a fi ve minute time delay to protect the compressor after 
it turns off. To temporarily bypass the fi ve minute delay, slide the Mode switch to 
OFF for 2 seconds and then back to Heat.
(Testing the thermostat continued on Page 10)
Cool  Off  Heat
Cool  Off  Heat
Testing the Thermostat