Страница из 14
7
FILTER
DIFF
ROOM
SET
REMOTE
3.  Temperature Differential (1°F to 3°F) (0.5°C to 1.5°C) – Set the number of degrees between 
your “setpoint” temperature and your “turn on” temperature.
 Press 
the  or 
 button to set differential value.
 Press 
the 
SW6 button to advance to the next screen.
Confi guration Mode Settings (continued)
FILTER
DIFF
ROOM
SET
REMOTE
FILTER
DIFF
ROOM
SET
REMOTE
5.  Maximum Heat Setpoint (55°F to 90°F) (13°C to 32°C) 
 
Adjust to control the maximum Heat set temperature allowed.
 Press 
the  or 
 button to select.
 Press 
the SW6 button to advance to the next screen.
FILTER
DIFF
ROOM
SET
REMOTE
FILTER
DIFF
ROOM
SET
REMOTE
4.  Minimum Cool Setpoint (45°F to 75°F) (7°C to 24.0°C) 
 
Adjust to control the minimum Cool set temperature allowed.
 Press 
the  or 
 button to select.
 Press 
the SW6 button to advance to the next screen.