10.  PERFORM STARTUP CHECkS AND ADjUSTMENTS
  FAILURE TO PERFORM THESE 
             CHECKS of the boiler's combustion and 
safety systems may result in serious property 
damage, injury, or death.
  IF YOU SMELL GAS, STOP and repair 
             the leak. Lighting the boiler when gas is 
leaking may cause explosion or fire.
Follow the checklist below:
1.
  Verify that the venting, water piping, gas 
piping, and electrical systems are properly 
installed and checked.
2.
  Apply power to the boiler.
3.
  Adjust zone thermostat to maximum setting.
4.
  Allow gas line to purge of air.
q
  Boiler lights cleanly within 60 seconds.
5.
  Adjust gas input rate. See Appendix F 
– Adjusting Gas Input Rate
10-a
q
  Pilot and main burner flames appear 
clean and blue.
6.
  Disconnect pilot lead wires from gas valve 
(Figure 10-b).
q
  Boiler shuts off.
7.
  Reconnect pilot lead wires to gas valve.
q
  Boiler restarts.
8.
  Adjust zone thermostat to minimum setting.
q
  Boiler shuts off.
9.
  Adjust zone thermostat to maximum setting.
10.
  Observe temperature gage as boiler heats.
11.
 Adjust the high limit setting to its minimum  
 level (see "Programming High Limit" in 
Section 8).
q
  Boiler shuts off when temperature gage 
 
     reads within 15°F of high limit setting.
12.
  Return high limit to the desired setting (see  
 "Programming High Limit" in Section 8).
13.
 Check draft. See Appendix G   
– Checking Draft and Combustion.
q
  No spillage observed.
14.
 Check combustion in the vent stack and 
record results in the spaces provided below.
  _____  CO
2
  (less than 7%)  
  _____  O
2
        (more than 9%)
  _____  CO       (less than 100 ppm, air free)
  ANY FAILED STARTUP CHECK 
             Must be corrected before placing the 
boiler in service.