Инструкция С Настройками для Burnham ES2 ES2

Скачать
Страница из 52
1
ANNUAL MAINTENANCE CHECkLIST
  
WARNINGS
THE BOILER CONTAINS REFRACTORY  
CERAMIC FIBER, a possible human carcinogen 
Use a NIOSH approved respirator when servicing 
high-temperature insulation and gasket materials.  
Wash exposed skin gently with soap and water 
after contact  Wash exposed clothing separate 
from normal laundry.
LABEL ALL WIRES prior to disconnection when 
servicing controls.  Wiring errors can cause 
improper and dangerous operation
FAILURE TO MAINTAIN THE BOILER in proper 
working condition may lead to fire, explosion, 
personal injury or death, and extensive property 
damage.
TURN OFF ALL GAS AND ELECTRIC power 
supplies to the boiler before servicing. Contact with 
or release of dangerous flammable gas, electrical 
voltage, moving parts, and very hot water under 
pressure may cause serious personal injury, 
property damage, or death. 
LOCK ELECTRICAL BOXES AND GAS VALVES 
CLOSED to prevent someone from inadvertently 
restoring power or gas before the heating system is 
safe to operate.
Equipment you will need:
q
   Soft bristle brush
q
   Bristle flue brush
q
   Vacuum with brush attachment
Perform these tasks each year:
1.
  Clean low water cutoff probe (if applicable).
2.
  Inspect vent for obstruction and signs of 
condensation, distortion, overheating or gas 
leakage.
3.
  Clean vent terminal and air intake screens.
4.
  Inspect boiler flue passages:
(1)   Remove vent pipe, damper.
(2)  Remove top panel and hood.
(3)   Remove blocked vent switch and   
  canopy. 
(4)   Examine all flue passageways.  Using  
  bristle flue brush and vacuum,    
  remove any soot or obstructions.
5
.  Remove and clean main burners:
(1)
   Remove jacket front panel.
(2)
   Disconnect pilot tubing at gas valve.
(3)
   Disconnect pilot lead wires at gas valve.
(4)
  Remove wires from flame roll-out switch.
(5)
   Remove burner access panel.
(6) 
  Mark location of the pilot main burner on  
       the manifold if the marking on manifold   
       is missing or obliterated.
AM-1
(7)
   Hold burner at throat.  Lift front of burner 
       to clear orifice (Figure AM-1). The  
   burner that holds the pilot can only be 
     removed by first lifting the burner  
   adjacent to its right.
6.
  Perform Startup Checks and Adjustments 
described earlier in this manual.
7.
  Check operation of airflow sensing switches.
8.
  Check for water leaks on the boiler or water 
pooling around boiler.
9.
  Manually operate the relief valve.  If the 
water is grey or black, there is excessive 
oxygen in the system.  Oxygen is corrosive 
to boilers.  Eliminate any source of oxygen.
10.
 Verify proper operation after servicing.