Инструкция С Настройками для Burnham ES2 ES2

Скачать
Страница из 52
43
APPENDIX E – FILLING THE SySTEM AND CHECkING FOR LEAkS
fill entire heating system with water and vent air from system.  Use the following procedure on a 
Series Loop or multi-zoned system installed as per the figure below. Remove air from system when filling.
1.
  Close full port ball valve located between 
vertical hose bib and air scoop in boiler 
supply piping (see Appendix D – System 
Piping.
2.
  Isolate all zones by closing zone valves or 
shut-off valves in supply and return of each 
zone(s).
3.
  Attach a hose to the vertical hose bib located 
prior to the full port ball valve in the system 
supply piping.
i        
  Terminate hose in five-gallon bucket at  
           a suitable floor drain or outdoor area.
4.
  Starting with one circuit at a time, open zone 
valve or shut-off valve in system supply and 
return piping.
5.
  Open hose bib.
6.
  Open fill valve (Make-up water line should 
be located directly after full port ball valve in 
system supply piping between air scoop and 
expansion tank).
7.
  Allow water to overflow from bucket until 
discharge from hose is bubble free for 30 
seconds.
8.
 
Close hose bib, continue filling the system 
until the pressure gauge reads 12 psi.  Close 
fill valve.
9.
 
Starting with the first convector in the loop, 
open air vent to purge air until a steady 
stream of water flows into container for 
approximately 5 seconds. Proceed to next 
convector and repeat procedure until all 
convectors in the loop are purged of air 
10.
  
Close the opened zone valve or shut-  
 off valve for the zone being purged of  
 air. 
11.
  
Open the zone valve or shut-off valve  
 for the next zone to be purged.  Repeat  
 the previous steps until all zones have  
 been purged.  At completion, open all  
 zone valves or shut-off valves.
12.
   Close hose bib, continue filling the system 
       until the pressure gauge reads 12 psi.   
 Close fill valve.  
i        
  If make-up water line is equipped  
     with pressure reducing valve, system 
           will automatically fill to 12 psi.  Follow fill  
           valve manufacturer’s instructions.
13.
 Open isolation valve in boiler supply piping.
14.
  Remove hose from hose bib.
Confirm that the boiler and system have no 
water leaks.
1.
  Check Rating Label for maximum operating 
pressure of this boiler. Never exceed this 
pressure during leak test. Do not plug or 
change pressure relief valve. Perform visual 
inspection for leaks or weeping joints after 
initial fill and during boiler warm-up period. 
Repair all leaks before placing boiler into 
permanent operation.  
2.
  If it is required to perform a long-term 
pressure leak test of the hydronic system, 
the boiler should first be isolated to avoid 
a pressure loss due to the escape of air 
trapped in the boiler.
3.
  To perform a long-term pressure test 
including the boiler, all trapped air must 
be removed from the boiler and system as 
prescribed above. A loss of pressure during 
such a test, with no visible leakage, is an 
indication that the boiler or system contained 
trapped air.