APPENDIX F – ADjUSTING GAS INPUT RATE
Natural Gas Boilers:
1.
  Turn off gas supply to all appliances other 
than gas-fired boiler.
2.
  Note the rated manifold gas pressure listed 
on the boiler’s rating label.
3.
  Connect Manometer to manifold pressure 
tapping on Gas Valve (Figure F-1).
4.
  Light main burners by adjusting thermostat 
to highest setting.
5.
  If required, adjust gas manifold pressure to 
the rated setting by turning the gas valves 
adjustment screw clockwise to decrease 
manifold pressure or counterclockwise to 
increase manifold pressure (Figure F-2). 
Several turns may be required.
  Do not force the adjustment screw.
6.
  On models using more than one gas valve, 
turn “off” the gas valve not having pilot 
control and first adjust the gas valve with 
pilot control. Then, turn “on” both gas valves 
and adjust the gas valve without pilot control.
7.
  Clock gas meter for at least two (2) 
revolutions of the dial typically labeled ½ or 
1 cubic foot per revolution on a residential 
gas meter. 
8.
  Determine gas flow rate in Cubic Feet 
per Hour based on elapsed time for two 
revolutions. (Example: 70 Seconds for (2) 
Revolutions = 102.8 Cu. Ft.
9.
  When the clocked time falls between two 
table values (Table F-1), add the table 
values shown above and below your clocked 
reading and divide by 2 (Example:  68 
Seconds for (2) Revolutions = (110.7+102.8) 
/2 = 106.7 Cu. Ft./Hr.).
10.
  Obtain gas-heating value (Btu per cubic  
 foot) from gas supplier or use nominal  
 value of 1000 Btu per cubic foot.
11.
  Multiply gas flow rate by gas heating value.  
 (Example: 70 Seconds for (2) Revolutions  
 = 120.8 Cu. Ft./Hr. X 1027 Btu/Cu. Ft. =  
 124,061 Btu/ Hr.
12.
  Compare measured input rate to input rate  
 stated on rating label.
  DO NOT EXCEED the boiler’s rated gas 
             input.
13. 
 If input is too high, reduce input rate by  
 
 decreasing manifold pressure. Do not  
 reduce more than 0.3” w.c. Instead, contact 
 
 Burnham for an orifice replacement kit.
14.
  If input is below 98% of Rating Label input,  
 increase manifold gas pressure no more  
 than 0.3 inches w.c. If measured rate is still  
 less than 98% of rated input, replace or re- 
 drill existing main burner gas orifices:
F-1