Repair Section
35
Defect (short or open) 
of freeze protection 
thermistor
When freeze protection thermistor
(connecting to J102) becomes short
or open. 
(Signal output (J106) turns on.)
Disconnect and reconnect the 
freeze protection thermistor.
If it doesn’t work, then change it.
Show running hours
Press ON/OFF and 
V
 buttons 
simultaneously for 3 sec, total 
operation hours of compressor is 
indicated by 6-digit (hours).
Example in left: 807 h
After 5 sec., display goes back to 
normal mode.
Show LCD and LED 
all on mode
Press HI/LO and 
U buttons 
simultaneously for 3 sec. 
(To check LCD segments and LED 
display.)
After 5 sec., display goes back to 
normal mode.
Key lock mode (LCD 
displays “LOCKED”.)
Press ENTER and SET CLOCK 
buttons simultaneously for 5 sec.
Press ENTER and SET CLOCK 
buttons simultaneously for 5 sec 
again to cancel the key lock mode.
Indication of model 
name
Press ENTER and SET CLOCK 
buttons simultaneously for 5 sec or 
turn on.
Reset to normal display 
automatically after 5 sec.
Detection of unit stop 
signal from fire alarm 
system
Press input signal from fire alarm 
becomes on.
(Unit stops, output signal (J106) 
turns on and buzzer sounds.)
1) After input signal turns off.
2) Reset the system.
To RESET: Press ON/OFF and
HI/LO buttons on the control box
simultaneously for 5 sec. 
LCD Display
Description
Condition
Reset/Remedy
F
SET TEMP
HI
ON
COOL
FAN
F
SET TEMP
HI
ON
COOL
FAN
START
STOP
CLOCK
MO TU WE TH FR
AM
F
C
F
C
PROGRAM
LOCKED
ON
PM
SA SU
SET TEMP
ROOM TEMP
HI
LO
ON
OFF
COOL
FAN
TU
AM
F
LOCKED
SET TEMP
HI
ON
COOL
FAN