Инструкции По Обслуживанию для Movincool OFFICEPRO63

Скачать
Страница из 77
Repair Section
36
Indication of service 
code
Press ON/OFF and 
U buttons 
simultaneously for 3 sec. Indication 
contents is as follows.
1) See page 36 and 37.
2) Press ON /OFF button.
Change model setting
For installing new controller PCB, if 
a different model name appears 
when the unit is reset or turned on, 
change model name according to 
the correct procedure.
1) While pressing 
U and V 
buttons, plug the power cord.
<Condition>
LCD indicates current setting 
model name and buzzer sounds.
2) After setting the model type by 
pressing 
U and V button, 
unplug the unit.
Activation of high 
pressure switch
When high pressure switch 
(connected to J104) activates 
(=J104 input turns to open) 3 times 
in 24 h, “HP” is indicated and signal 
output (J106) turns on.
When it activates 10 times in 24 h, 
“FAIL HP” is indicated and buzzer 
sounds.
Find the cause of high pressure to 
address it.
Check the following.
Ambient air temperature
(65 °F (18.3 °C),
 50
 %
RH
95 °F (35 °C), 60 %RH)
Air filter (if dirty, wash up.) 
Condenser fan motor (if not 
working, replace.) Defect of high 
pressure switch (if switch is open 
when unit is off, replace switch.) 
Reset the system.
To RESET: Press ON/OFF and 
HI/LO buttons on the control box 
simultaneously for 5 sec.
LCD Display
Description
Condition
Reset/Remedy
LCD
DF
FZ
OD
Description
Value
Defrost status
Evap. out pipe
temperature
26
109F
(“26”
“X9”)
Outdoor
temperature
0 (“00”)
TU
AM
F
SET TEMP
HI
ON
COOL
FAN